Pipeline Safety: Dangers of Abnormal Snow and Ice Build-Up on Gas
Distribution Systems
AGENCY: Pipeline and Hazardous Materials Safety Administration (PHMSA),
DOT.
ACTION: Notice; Issuance of Advisory Bulletin.
-----------------------------------------------------------------------
SUMMARY: Recent events on natural gas distribution system facilities
appear to be related to either the stress of snow and ice or
malfunction of pressure control equipment due to ice blockage of
pressure control equipment vents by ice. This advisory bulletin advises
owners and operators of gas pipelines of the need to take steps to
prevent damage to pipeline facilities from accumulated snow or ice.
FOR FURTHER INFORMATION CONTACT: Alan Mayberry at (202) 366-5124, or by
e-mail at alan.mayberry@dot.gov.
SUPPLEMENTARY INFORMATION:
I. Background
The accumulation of snow and ice increases the potential for damage
to meters and regulators and other pipeline facilities. Several
accidents occurring during the winter of 2007/2008 on natural gas
distribution system facilities appear to be related to either the
stress of snow and ice or malfunction of pressure control equipment due
to ice blockage of pressure control equipment vents. Exposed piping at
metering and pressure regulating stations, at service regulators, and
at propane tanks, are at greatest risk. Damage may result from the
stresses imposed by the additional loading of the snow or ice. Damage
to facilities may also result from the impact of snow or ice falling
from roofs, or ice forming in or on regulators preventing their proper
operation, or shoveling snow from roofs to protect dwellings from
abnormal snow accumulation.
II. Advisory Bulletin (ADB-08-03)
To: Owners and Operators of Petroleum Gas and Natural Gas
Facilities in Areas Subject to Heavy Snowfall or Abnormally Icy
Weather.
Subject: Dangers of Abnormal Snow and Ice Build-up on Gas
Distribution Systems.
Purpose: To inform owners and operators of the need (1) to monitor
the potential impact of excessive snow and ice on these facilities; and
(2) to inform the public about possible hazards from snow and ice
accumulation on regulators and other pipeline facilities.
Advisory: PHMSA is advising operators of gas pipeline facilities,
regardless of whether those facilities are regulated by PHMSA or state
agencies, to consider the following steps to address the safety risks
from accumulated snow and ice on pipeline facilities:
1. Notify customers and other entities of the need for caution
associated with excessive accumulation and removal of snow and ice.
Notice should include the need to clear snow and ice from exhaust and
combustion air vents for gas appliances to prevent accumulation of
carbon monoxide in buildings or operational problems for the combustion
equipment.
2. Pay attention to snow and ice related situations that may cause
operational problems for pressure control and other equipment.
3. Monitor the accumulation of moisture in equipment and snow or
ice blocking regulator or relief valve vents which could prevent
regulators and relief valves from functioning properly.
4. The piping on service regulator sets is susceptible to damage
that could result in failure if caution is not exercised in cleaning
snow from around the equipment. Where possible, use a broom, instead of
a shovel to clear snow off regulators, meters, associated piping,
propane tanks, tubing, gauges or other propane system appurtenances.
5. Remind the public to contact the gas company or designated
emergency response officials if there is an odor of gas present or if
gas appliances are not functioning properly. Also remind the public
that, if there is a gas or propane odor, occupants should leave the
residence immediately and contact their gas company, propane operator
or designated emergency response officials.