[Federal Register: December 12, 2005 (Volume 70, Number 237)]
[Proposed Rules]               
[Page 73523-73552]
From the Federal Register Online via GPO Access [wais.access.gpo.gov]
[DOCID:fr12de05-27]                         


[[Page 73523]]

-----------------------------------------------------------------------

Part III





Environmental Protection Agency





-----------------------------------------------------------------------



40 CFR Part 112



Oil Pollution Prevention; Spill Prevention, Control, and Countermeasure 
Plan Requirements--Amendments; Proposed Rule


[[Page 73524]]


-----------------------------------------------------------------------

ENVIRONMENTAL PROTECTION AGENCY

40 CFR Part 112

[EPA-HQ-OPA-2005-0001; FRL-8007-2]
RIN 2050-AG23

 
Oil Pollution Prevention; Spill Prevention, Control, and 
Countermeasure Plan Requirements--Amendments

AGENCY: Environmental Protection Agency.

ACTION: Proposed rule.

-----------------------------------------------------------------------

SUMMARY: The Environmental Protection Agency (EPA or the Agency) is 
today proposing to amend the Spill Prevention, Control, and 
Countermeasure (SPCC) Plan requirements to reduce the regulatory burden 
for certain facilities by: Providing an option that would allow owners/
operators of facilities that store less than 10,000 gallons of oil and 
meet other qualifying criteria to self-certify their SPCC Plans, in 
lieu of review and certification by a Professional Engineer; providing 
an alternative to the secondary containment requirement, without 
requiring a determination of impracticability, for facilities that have 
certain types of oil-filled equipment; defining and providing an 
exemption for motive power containers; and exempting airport mobile 
refuelers from the specifically sized secondary containment 
requirements for bulk storage containers. In addition, the Agency also 
proposes to remove and reserve certain SPCC requirements for animal 
fats and vegetable oils and proposes a separate extension of the 
compliance dates for farms. In proposing these changes, EPA is 
significantly reducing the burden imposed on the regulated community in 
complying with the SPCC requirements, while maintaining protection of 
human health and the environment. Further, the Agency requests comments 
on the potential scope of future rulemaking. In a separate document in 
today's Federal Register, the Agency is proposing to extend the 
compliance dates for all facilities.

DATES: Comments must be received on or before February 10, 2006.

ADDRESSES: Submit your comments, identified by Docket ID No. EPA-HQ-
OPA-2005-0001 by one of the following methods:
     Federal Rulemaking Portal: http://www.regulations.gov. Follow the 

on-line instructions for submitting comments.
     Mail: The mailing address of the docket for this 
rulemaking is EPA Docket Center (EPA/DC), Docket ID No. EPA-HQ-OPA-
2005-0001, 1200 Pennsylvania Avenue, NW., Washington, DC 20460.
     Hand Delivery: Such deliveries are only accepted during 
the Docket's normal hours of operation, and special arrangements should 
be made for deliveries of boxed information.
    Instructions: Direct your comments to Docket ID No. EPA-HQ-OPA-
2005-0001. EPA's policy is that all comments received will be included 
in the public docket without change and may be made available online at 
http://www.regulations.gov, including any personal information provided, 

unless the comment includes information claimed to be Confidential 
Business Information (CBI) or other information whose disclosure is 
restricted by statute. Do not submit information that you consider to 
be CBI or otherwise protected through http://www.regulations.gov. The 

http://www.regulations.gov Web site is an ``anonymous access'' system, which 

means EPA will not know your identity or contact information unless you 
provide it in the body of your comment. If you submit an electronic 
comment, EPA recommends that you include your name and other contact 
information in the body of the comment and with any disk or CD-ROM you 
submit. If EPA cannot read your comment due to technical difficulties 
and cannot contact you for clarification, EPA may not be able to 
consider your comment. Electronic files should avoid the use of special 
characters, any form of encryption, and be free of any defects or 
viruses. Comments and suggestions regarding the scope of any future 
rulemaking should be clearly differentiated from comments specific to 
today's proposal (e.g., label Suggestions for Future Rulemaking and 
Comments on Current Proposal).
    Docket: All documents in the docket are listed in the 
http://www.regulations.gov index. Although listed in the index, some 

information is not publicly available, e.g., CBI or other information 
whose disclosure is restricted by a statute. Certain other material, 
such as copyrighted material, will be publicly available only in hard 
copy. Publicly available docket materials are available either 
electronically in http://www.regulations.gov or in hard copy at the EPA 

Docket, EPA/DC, EPA West, Room B102, 1303 Constitution Ave., NW., 
Washington, DC. The Public Reading Room is open from 8:30 a.m. to 4:30 
p.m., Monday through Friday, excluding legal holidays. The telephone 
number for the Public Reading Room is 202-566-1744, and the telephone 
number to make an appointment to view the docket is 202-566-0276.

FOR FURTHER INFORMATION CONTACT: For general information, contact the 
Superfund, TRI, EPCRA, RMP and Oil Information Center at 800-424-9346 
or TDD 800-553-7672 (hearing impaired). In the Washington, DC 
metropolitan area, call 703-412-9810 or TDD 703-412-3323. For more 
detailed information on specific aspects of this proposed rule, contact 
either Vanessa E. Rodriguez at 202-564-7913 
rodriguez.vanessa@epa.gov), or Mark W. Howard at 202-564-1964 
howard.markw@epa.gov), U.S. Environmental Protection Agency, 1200 
Pennsylvania Avenue, NW., Washington, DC, 20460-0002, Mail Code 5104A.

SUPPLEMENTARY INFORMATION: This proposed rule would amend the 
requirements for Spill Prevention, Control, and Countermeasure (SPCC) 
Plans in 40 CFR part 112. First, the proposal would provide an 
alternative option for the owner/operator of a facility that meets 
specific qualifying criteria (hereafter referred to as a ``qualified 
facility'') to self-certify that the facility's SPCC Plan complies with 
40 CFR part 112, in lieu of the requirement for a Professional 
Engineer's (PE) review and certification. Second, the proposal would 
provide an alternative option for the owner/operator of a facility with 
oil-filled operational equipment that meets specific qualifying 
criterion (hereafter referred to as ``qualified oil-filled operational 
equipment'') to establish and document an inspection or monitoring 
program, prepare a contingency plan, and provide a written commitment 
of manpower, equipment and materials in lieu of secondary containment 
for qualified oil-filled operational equipment without being required 
to make an individual impracticability determination. Third, the 
proposal would define and provide an exemption for motive power 
containers. Fourth, the proposal would exempt airport mobile refuelers 
from specifically sized secondary containment requirements for bulk 
storage containers. Fifth, the proposal removes and reserves certain 
SPCC requirements for animal fats and vegetable oils. Finally, the 
proposal provides a separate extension of the compliance dates for 
farms and, in a separate notice in today's Federal Register, the Agency 
is proposing to extend the compliance dates for all facilities. The 
contents of this preamble are:

I. General Information

[[Page 73525]]

II. Entities Potentially Affected by This Proposed Rule
III. Statutory Authority and Delegation of Authority
IV. Background
V. Today's Action
    A. Qualified Facilities
    1. Eligibility Criteria
    a. Total Facility Oil Storage Capacity Threshold
    b. Reportable Discharge History
    2. Proposed Requirements for Qualified Facilities
    a. Self-Certification and Plan Amendments
    b. Environmental Equivalence and Impracticability Determinations
    c. SPCC Plan Exceptions
    3. Alternative Options Considered
    a. Extension/Suspension Options
    b. Multi-tiered Structure
    c. One-time Notification
    B. Qualified Oil-filled Operational Equipment
    1. Proposed Oil-Filled Operational Equipment Definition
    2. Eligibility Criteria--Reportable Discharge History
    3. Proposed Requirements for Qualified Oil-Filled Operational 
Equipment In Lieu of Secondary Containment
    a. Contingency Plans and a Written Commitment of Manpower, 
Equipment and Materials
    b. Inspections or Monitoring Program
    4. Alternative Options Considered
    a. Capacity Threshold Qualifier
    b. Multi-Tiered Structure
    c. Extension/Suspension Options
    5. Qualified Facilities and Qualified Oil-Filled Operational 
Equipment Overlap
    C. Motive Power
    1. Definition of Motive Power
    2. Proposed Exemption
    3. Alternative Options Considered
    a. Equipment-Based Motive Power Exemption
    b. Threshold-Based Motive Power Exemption
    c. Exclusion From Storage Capacity Calculation
    D. Airport Mobile Refuelers
    1. Definition of Airport Mobile Refueler
    2. Proposed Amended Requirements
    E. Animal Fats and Vegetable Oils
VI. Proposed Extension of Compliance Dates for Farms
    A. Eligibility Criteria
    B. Proposed Compliance Date Extension for Farms
VII. Statutory and Executive Order Reviews
    A. Executive Order 12866--Regulatory Planning and Review
    B. Paperwork Reduction Act
    C. Regulatory Flexibility Act
    D. Unfunded Mandates Reform Act
    E. Executive Order 13132--Federalism
    F. Executive Order 13175--Consultation and Coordination With 
Indian Tribal Governments
    G. Executive Order 13045--Protection of Children From 
Environmental Health & Safety Risks
    H. Executive Order 13211--Actions That Significantly Affect 
Energy Supply, Distribution, or Use
    I. National Technology Transfer and Advancement Act

I. General Information

    To reduce regulatory burden for qualified facilities and to address 
several concerns involving oil-filled operational equipment, motive 
power containers, airport mobile refuelers, and provisions specific to 
animal fats and vegetable oils, EPA proposes to amend the SPCC Plan 
requirements in 40 CFR part 112. The Agency also proposes a separate 
extension of the compliance dates for farms. Specifically:
     EPA proposes an alternative option for the owner/operator 
of a qualified facility to self-certify his/her SPCC Plan, prepared in 
accordance with 40 CFR part 112, in lieu of review and certification by 
a Professional Engineer (PE). A qualified facility is a facility 
subject to the SPCC requirements that (1) has a maximum total facility 
oil storage capacity of 10,000 gallons or less; and (2) had no 
reportable oil discharge as described in Sec.  112.1(b) during the ten 
years prior to self-certification or, since becoming subject to the 
SPCC requirements if the facility has been in operation for less than 
ten years. Under this proposed approach, facility owners/operators of 
qualified facilities choosing to self-certify their SPCC Plans may not 
deviate from any requirement of the SPCC rule under Sec.  112.7(a)(2) 
(with two exceptions) and may not make impracticability determinations 
in their SPCC Plans as described under Sec.  112.7(d). The two 
exceptions are that facility owners/operators of qualified facilities 
choosing to self-certify their SPCC Plans would have flexibility with 
respect to the security requirements and container integrity testing.
     EPA proposes a definition for oil-filled operational 
equipment and proposes that owners and operators of facilities where 
qualified oil-filled operational equipment is located have the 
alternative of preparing an oil spill contingency plan and a written 
commitment of manpower, equipment and materials, without having to 
determine that secondary containment is impracticable on an individual 
equipment basis (make an individual impracticability determination as 
required in Sec.  112.7(d)); and establish and document an inspection 
or monitoring program for this equipment to detect equipment failure 
and/or a discharge in lieu of providing secondary containment for 
qualified oil-filled operational equipment. Today's proposal would 
eliminate the current requirement for an individual impracticability 
determination for oil-filled operational equipment at a facility that 
has had no discharges as described in Sec.  112.1(b) from any oil-
filled operational equipment during the ten years prior to the Plan 
certification date or, since becoming subject to the SPCC requirements 
if the facility has been in operation for less than ten years.
     EPA proposes to exempt from the SPCC rule certain motive 
power containers. Motive power containers are onboard bulk storage 
containers used solely to power the movement of a motor vehicle (i.e., 
fuel tanks), or ancillary onboard oil-filled operational equipment 
(i.e., hydraulics and lubrication systems) used solely to facilitate 
its operation. This exemption would not apply to transfers of fuel or 
other oil into motive power containers at an otherwise regulated 
facility. This exemption would not apply to a bulk storage container 
mounted on a vehicle for any purpose other than powering the vehicle 
itself, for example, a tanker truck or mobile refueler. Additionally, 
this exemption would not apply to oil drilling or workover equipment, 
including rigs.
     EPA proposes to exempt airport mobile refuelers from the 
specifically sized secondary containment requirements for bulk storage 
containers under Sec.  112.8(c)(2) and (11) of the SPCC rule. Airport 
mobile refuelers are vehicles found at airports that have onboard bulk 
storage containers designed for, or used to, store and transport fuel 
for transfer into or from an aircraft or ground service equipment. The 
remaining provisions of Sec.  112.8(c) and the general secondary 
containment requirements of Sec.  112.7(c) would still apply to the 
onboard bulk storage containers on airport mobile refuelers and the 
transfers associated with this equipment.
     The Agency proposes to amend the requirements for animal 
fats and vegetable oils in Subpart C of Part 112 by removing Sec.  
112.13 (requirements for onshore oil production facilities), Sec.  
112.14 (requirements for onshore oil drilling and workover facilities), 
and Sec.  112.15 (requirements for offshore oil drilling, production, 
or workover facilities) because these sections do not apply to 
facilities that handle, store, or transport animal fats and vegetable 
oils.
     EPA proposes to extend the compliance dates for farms, 
while the Agency considers whether the unique nature of this sector 
warrants differentiated requirements under the SPCC rule.
     Under the current regulations in Sec.  112.3(a), (b) and 
(c), a facility that was in operation on or before August 16, 2002 must 
make any necessary amendments to its SPCC Plan by February 17, 2006, 
and fully implement

[[Page 73526]]

its SPCC Plan by August 18, 2006. A facility that came into operation 
after August 16, 2002 but before August 18, 2006, must prepare and 
fully implement an SPCC Plan on or before August 18, 2006. The owner or 
operator of an onshore or offshore mobile facility must maintain their 
Plan, but must amend and implement it, if necessary to ensure 
compliance with this part, on or before August 18, 2006. In a separate 
notice in today's Federal Register, the Agency is proposing to extend 
the compliance dates for all facilities to October 31, 2007. Reviewers 
should refer to that notice for a complete discussion of the proposed 
extension. Regarding modifications of the SPCC regulations, to the 
extent practicable, EPA will establish deadlines for compliance 
implementation that commence one year after promulgating the regulatory 
revisions.

         II. Entities Potentially Affected by This Proposed Rule
------------------------------------------------------------------------
            Industry category                        NAICS code
------------------------------------------------------------------------
Crop and Animal Production...............                        111-112
Crude Petroleum and Natural Gas                                      211
 Extraction..............................
Coal Mining, Non-Metallic Mineral Mining         2121/2123/213114/213116
 and Quarrying...........................
Electric Power Generation, Transmission,                            2211
 and Distribution........................
Heavy Construction.......................                            234
Petroleum and Coal Products Manufacturing                            324
Other Manufacturing (including animal                              31-33
 fats and vegetable oil manufacturing)...
Petroleum Bulk Stations and Terminals....                          42271
Automotive Rental and Leasing............                           5321
Gasoline Service Stations................                            447
Fuel Oil Dealers.........................                           4543
Waste Management and Remediation.........                            562
Other Commercial Facilities (including               44-45, 51-55, 56172
 Retail Stores, Apartment Buildings,
 Wholesalers and Janitorial Services)....
Transportation (including Pipelines and       482-486/488112-48819/4883/
 Airports), Warehousing, and Marinas.....            48849/492-493/71393
Elementary and Secondary Schools,                                    611
 Colleges................................
Federal, State, Local Government and                                  92
 Military Installations..................
Hospitals/Nursing and Residential Care                           621-623
 Facilities..............................
------------------------------------------------------------------------

    The list of potentially affected entities in the above table may 
not be exhaustive. The Agency's aim is to provide a guide for readers 
regarding those entities that potentially could be affected by this 
action. However, this action may affect other entities not listed in 
this table. If you have questions regarding the applicability of this 
action to a particular entity, consult the person listed in the 
preceding section entitled FOR FURTHER INFORMATION CONTACT.

III. Statutory Authority and Delegation of Authority

    Section 311(j)(1)(C) of the Clean Water Act (CWA or the Act), 33 
U.S.C. 1321(j)(1)(C), requires the President to issue regulations 
establishing procedures, methods, equipment, and other requirements to 
prevent discharges of oil from vessels and facilities and to contain 
such discharges. The President delegated the authority to regulate non-
transportation-related onshore facilities to the EPA in Executive Order 
11548 (35 FR 11677, July 22, 1970), which has been replaced by 
Executive Order 12777 (56 FR 54757, October 22, 1991). A Memorandum of 
Understanding (MOU) between the U.S. Department of Transportation (DOT) 
and EPA (36 FR 24080, November 24, 1971) established the definitions of 
transportation- and non-transportation-related facilities. An MOU among 
EPA, the U.S. Department of Interior (DOI), and DOT, effective February 
3, 1994, has redelegated the responsibility to regulate certain 
offshore facilities from DOI to EPA.

IV. Background

    On July 17, 2002, EPA published a final rule amending the Oil 
Pollution Prevention regulation (40 CFR part 112) promulgated under the 
authority of section 311(j) of the CWA. This revised rule included 
requirements for SPCC Plans and for Facility Response Plans (FRPs). It 
also included new subparts outlining the requirements for various 
classes of oil; revised the applicability of the regulation; amended 
the requirements for completing SPCC Plans; and made other 
modifications (67 FR 47042). The revised rule became effective on 
August 16, 2002. After publication of this rule, several members of the 
regulated community filed legal challenges to certain aspects of the 
rule. Most of the issues raised in the litigation have been settled, 
following which EPA published clarifications in the Federal Register to 
several aspects of the revised rule (69 FR 29728, May 25, 2004).\1\
---------------------------------------------------------------------------

    \1\ American Petroleum Institute v. Leavitt, No. 1:102CV02247 
PLF and consolidated cases (D.D.C. filed Nov. 14, 2002). The 
remaining issue to be decided concerns the definition of ``navigable 
waters'' in Sec.  112.1.
---------------------------------------------------------------------------

    EPA has extended the dates for revising and implementing revised 
SPCC Plans in 40 CFR 112.3(a) and (b) several times, and has extended 
the compliance date for 40 CFR 112.3(c) (see 69 FR 48794 (August 11, 
2004) for further discussion on the extensions). This action was taken 
by EPA in order to provide the regulated community with sufficient time 
to comply with the 2002 revised rule and to allow the regulated 
community time to understand the 2004 clarifications and be able to 
incorporate them in their updated SPCC Plans. The current deadline for 
the preparation and certification of revised SPCC Plans for facilities 
maintaining their current SPCC Plan is February 17, 2006. Plans must be 
implemented by August 18, 2006. Facilities that became subject to the 
SPCC rule after August 16, 2002 are currently required to develop and 
implement their Plans by August 18, 2006.
    On September 20, 2004, EPA published two Notices of Data 
Availability (NODAs). The first NODA made available and solicited 
comments on submissions to EPA suggesting more focused requirements for 
facilities subject to the SPCC rule that handle oil below a certain 
threshold amount, referred to as ``certain facilities'' (69 FR 56182). 
Streamlined approaches for facilities with oil capacities below a 
certain threshold were discussed in the NODA documents. The second NODA 
made available and solicited comments

[[Page 73527]]

on whether alternate regulatory requirements would be appropriate for 
facilities with oil-filled and process equipment (69 FR 56184). EPA has 
reviewed the public comments and data submitted in response to the 
NODAs in developing today's proposal.
    In addition, the Agency considered regulatory relief for airport 
mobile refuelers in response to concerns raised by the aviation sector. 
Airport mobile refuelers are vehicles that are used on an airport 
facility to refuel aircraft and ground service equipment (such as belt 
loaders, tractors, luggage transport vehicles, deicing equipment, and 
lifts) used at airports. The onboard bulk storage containers on airport 
mobile refuelers that are used to transport and transfer fuel into or 
from aircraft and ground service equipment are considered mobile or 
portable bulk storage containers under the SPCC rule because they are 
used to store oil prior to further distribution and use. As such, they 
are subject to all applicable SPCC rule provisions, including the sized 
secondary containment provisions of Sec.  112.8(c)(2) and (11). These 
provisions require the secondary containment, such as a dike or 
catchment basin, to be sufficient to contain the capacity of the 
largest single compartment or container and include sufficient 
freeboard to contain precipitation.
    Regulated community members in the aviation sector have expressed 
concern that requiring such sized secondary containment for airport 
mobile refuelers is not practicable for safety and security reasons. 
(Included in the Docket for today's proposal are the letters that have 
been submitted to EPA regarding this matter.) Specifically, it has been 
argued that to require these refuelers to park in specially designed 
secondary containment areas located within an airport's aircraft 
operations area could create a safety and security hazard because it 
would require grouping of the vehicles or place impediments in the 
operations area. Additionally, requiring mobile refuelers to return to 
containment areas located within the airport's tank farm between 
refueling operations may increase the risk of accidents (and therefore 
accidental oil discharge), as the vehicles would travel with increased 
frequency through the busy aircraft operations area. EPA acknowledges 
these concerns and seeks to provide relief for airport mobile refuelers 
from the specifically sized secondary containment requirements for bulk 
storage containers, while protecting the environment from refueler 
spills, particularly those associated with transfers. Consequently, 
these refuelers remain subject to the other bulk storage container 
requirements under Sec.  112.8(c) and the general secondary containment 
requirements under Sec.  112.7(c) which also applies to the transfers 
of oil associated with airport mobile refuelers.
    In contrast to a mobile or portable bulk storage container such as 
a mobile refueler, a ``motive power container'' is an integral part of 
a motor vehicle (including aircraft), providing fuel for propulsion or 
providing some other operational function, such as lubrication of 
moving parts or for operation of onboard hydraulic equipment. Motive 
power containers on vehicles used solely at non-transportation related 
facilities fall under EPA jurisdiction and are subject to the SPCC 
regulation. Examples of motive power vehicles include, but are not 
limited to: buses; recreational vehicles; some sport utility vehicles; 
construction vehicles; aircraft; farm equipment; and earthmoving 
equipment (e.g., such as at a drilling or workover facility). Examples 
of facilities or locations that may be covered by the SPCC requirements 
solely because of the presence of motive power containers include, but 
are not limited to, heavy equipment dealers, commercial truck dealers, 
and parking lots.
    While the concept of ``motive power'' is not directly addressed in 
the SPCC regulation, such vehicle fuel containers may fall under the 
definition of ``bulk storage container'' in Sec.  112.2, while the 
onboard lubrication system may be considered oil-filled operational 
equipment. Therefore, motive power containers which store oil used for 
the propulsion of a vehicle are subject to all the requirements under 
Sec.  112.8(c) if they have a capacity of 55 gallons or more. These 
requirements include specifically sized secondary containment for bulk 
storage containers, integrity testing (visual plus non-destructive 
testing), and a requirement to engineer containers to avoid discharges 
(such as an overfill alarm). Additionally, any oil-filled operational 
equipment with a capacity of 55 gallons or more mounted on a vehicle 
are subject to the general secondary containment requirements listed in 
Sec.  112.7(c).
    EPA recognizes that, in most cases, the requirements of Sec.  
112.8(c), including specifically sized secondary containment and the 
general secondary containment requirements under Sec.  112.7(c), are 
not practicable for motive power containers. It has never been EPA's 
intent to regulate motive power containers. Therefore, EPA is proposing 
to exempt such motive power containers from the SPCC regulation.
    In the July 17, 2002 final SPCC rule, the Agency promulgated 
general requirements for SPCC Plans for all facilities and all types of 
oil in Sec.  112.7. In response to the Edible Oil Regulatory Reform Act 
(EORRA), EPA promulgated separate subparts in part 112 for facilities 
storing or using various classes of oil, but the requirements in each 
subpart are the same. EORRA required most Federal agencies to 
differentiate between and establish separate classes for various types 
of oil, specifically, between animal fats and oils and greases, and 
fish and marine mammal oils and oils of vegetable origin, including 
oils from seeds, nuts, and kernels; and other oils and greases, 
including petroleum. The result of this approach was that the new 
Subpart C included requirements for animal fat and vegetable oil (AFVO) 
facilities--onshore facilities (excluding production facilities) (Sec.  
112.12), onshore oil production facilities, (Sec.  112.14) onshore oil 
drilling and workover facilities (Sec.  112.13), and requirements for 
offshore oil drilling, production, or workover facilities (Sec.  
112.15). While the Agency recognized that some of these requirements 
are not applicable to facilities that handle, store or transport AFVO, 
these sections were promulgated because the Agency had not proposed 
differentiated SPCC requirements for public notice and comment. As a 
result, the current requirements for petroleum oils were also applied 
to animal fats and vegetable oils. EPA is today proposing to remove 
those sections from the SPCC requirements that are not applicable or 
appropriate to animal fats and vegetable oils.
    Additionally, EPA has issued the SPCC Guidance for Regional 
Inspectors. The guidance document is intended to assist regional 
inspectors in reviewing a facility's implementation of the SPCC rule. 
The document is designed to facilitate an understanding of the rule's 
applicability, to help clarify the role of the inspector in the review 
and evaluation of the performance-based SPCC requirements, and to 
provide a consistent national policy on several SPCC-related issues. 
The guidance is also available to both the owners and operators of 
facilities that may be subject to the requirements of the SPCC rule and 
to the general public on the Agency's website at http://www.epa.gov/oilspill. 

This guidance is a living document and will be revised, as necessary, 
to reflect any relevant future regulatory amendments in a timely 
manner. Accordingly, EPA welcomes comments from the regulated community 
and the public on the guidance document within 60 days of this NPRM, as 
described on the website.

[[Page 73528]]

The guidance document is a separate effort from this rulemaking. EPA 
does not plan to address comments on the guidance document when taking 
final action on this rule. Comments on the guidance document should not 
be submitted to the docket for this rulemaking. Refer to the website 
http://www.epa.gov/oilspill for the text of the guidance document and for 

instructions for providing suggestions on the guidance document. The 
EPA urges readers to review the guidance document for assistance in 
understanding the SPCC rule and today's proposal. Pursuant to today's 
proposal, EPA anticipates issuing an updated guidance document in 2006 
to reflect finalization of this rulemaking such that inspectors and the 
regulated community have accurate and timely information on SPCC 
requirements.
    Although the scope of today's proposal was originally intended to 
address only certain targeted areas of the SPCC requirements, the 
Agency is including several additional proposed modifications to 
address a number of issues and concerns raised by the regulated 
community. As highlighted in the EPA Regulatory Agenda and the 2005 OMB 
report on ``Regulatory Reform of the U.S. Manufacturing Sector,'' there 
are other issues under consideration for possible future rulemaking 
action. The modifications proposed today do not preclude a future 
rulemaking on other issues not addressed in today's proposal. Rather, 
EPA is working to identify additional areas where regulatory reform may 
be appropriate. For these additional areas, the Agency expects to issue 
a proposed rule in 2007. Additionally, EPA in conjunction with DOE will 
be conducting an energy impact analysis of the SPCC requirements, and 
will consider the results of this analysis to inform the Agency's 
deliberations over any future rulemaking. EPA is interested in whether 
there are other aspects of the SPCC regulatory requirements, beyond 
those that are addressed in today's proposal, that should be the focus 
of future rulemaking. The Agency also requests that commenters who 
provide suggestions regarding future rulemaking clearly differentiate 
them from comments submitted on today's proposal (e.g., label 
Suggestions for Future Rulemaking and Comments on Current Proposal). 
The Agency will not address these suggestions when taking final action 
on this proposed rule, but will take them into consideration in future 
rulemaking decisions.

V. Today's Action

A. Qualified Facilities

    EPA proposes to amend the Oil Pollution Prevention regulation (40 
CFR part 112) to provide an option to allow the owner or operator of a 
facility that meets the qualifying criteria (hereafter referred to as a 
``qualified facility'') to self-certify the facility's SPCC Plan in 
lieu of certification by a licensed professional engineer (PE). EPA 
proposes to amend Sec.  112.3 to describe the SPCC eligibility criteria 
that a regulated facility must meet in order to be considered a 
qualified facility. A qualified facility would be a facility subject to 
the SPCC rule that (1) has an aggregate facility oil storage capacity 
of 10,000 gallons or less; and (2) had no discharges as described in 
Sec.  112.1(b) during the ten years prior to self-certification or 
since becoming subject to the SPCC requirements if less than ten years. 
Facilities that have been subject to SPCC for less than ten years, 
including new facilities, would need to demonstrate no discharges as 
described in Sec.  112.1(b) only for the period of time they have been 
subject to the SPCC rule. Self-certified Plans would not be allowed to 
include ``environmentally equivalent'' alternatives to required Plan 
elements as provided in Sec.  112.7(a)(2) or to claim impracticability 
with respect to any secondary containment requirements as provided in 
Sec.  112.7(d). The two exceptions for which the owner and operator 
would still be allowed to use environmentally equivalent measures are 
with respect to security and integrity testing. Facilities with 
complicated operations and lower capacities may find that the current 
rule offers a more cost-effective method of achieving compliance than 
the proposed option. Therefore, a qualified facility could choose to 
follow the current SPCC requirements (including the PE certification) 
to take advantage of the flexibility offered by PE-certified 
impracticality determinations and environmentally equivalent measures.
1. Eligibility Criteria
a. Total Facility Oil Storage Capacity Threshold
    EPA proposes to limit qualified facilities to a total maximum 
storage capacity of 10,000 gallons of oil. EPA considered many 
different factors before selecting this storage capacity. First, EPA 
has established 10,000 gallons as a threshold in several other rules 
relating to oil discharges. This threshold quantity is used in the 
National Oil and Hazardous Substances Pollution Contingency Plan 
(National Contingency Plan or NCP) to classify oil discharges based on 
the location and size of the discharge (see 40 CFR 300.5). The NCP 
refers to discharges greater than 10,000 gallons to inland waters as 
``major,'' while other thresholds are used to classify ``minor'' and 
``medium'' discharges. The classes are provided as guidance to the On-
Scene Coordinator (OSC), and serve as criteria for the actions 
delineated in the NCP. It is important to note, however, that the NCP 
quantitative thresholds are only provided to help the OSC determine 
response action, and do not imply associated degrees of hazard to the 
public health or welfare, or environmental damage. The NCP size classes 
nevertheless define an oil discharge to inland waters exceeding 10,000 
gallons as a major discharge.
    A discharge of 10,000 gallons or more is also one of the factors 
used in identifying facilities that must prepare and submit a Facility 
Response Plan (FRP) under Sec.  112.20(f)(1). The FRP rule applies to 
facilities that could reasonably be expected to cause substantial harm 
to the environment due to a discharge to waters of the U.S. and 
adjoining shorelines.
    Second, state regulations also provide support for the use of a 
10,000-gallon threshold. A number of states differentiate regulatory 
requirements based on a facility's total storage capacity, with some 
states specifying a 10,000-gallon threshold. For example, Maryland 
requires that all commercial facilities storing more than 10,000 
gallons of oil obtain an oil operations permit; Minnesota requires 
facilities storing between 10,000 and 1,000,000 gallons of oil to 
prepare a prevention and response plan; and Oregon places special 
requirements on marine facilities storing more than 10,000 gallons of 
oil. The 10,000-gallon threshold is also frequently used in setting 
requirements for certain storage tanks. For example, New York requires 
a ``secondary containment system'' around all aboveground storage tanks 
(ASTs) with a storage capacity greater than or equal to 10,000 gallons, 
and Wisconsin caps the size of ASTs that can be used for fueling 
vehicles at 10,000 gallons.
    Finally, 10,000 gallons is a common storage tank size, and EPA 
believes that setting a maximum capacity at 10,000 gallons would 
address the concerns that smaller facilities have raised. In fact, the 
Small Business Administration Office of Advocacy suggested that a 
10,000-gallon threshold is a reasonable volume to address the concerns 
of facilities with relatively smaller volumes of oil. The Agency seeks 
comments on whether this

[[Page 73529]]

threshold appropriately addresses the concerns of facilities with 
relatively smaller volumes of oil, while maintaining the environmental 
protection intended by the regulation. If commenters suggest 
alternative volume thresholds, it will be important for the comments to 
also include a justification for such alternative volume thresholds in 
order for the Agency to adequately consider the comments submitted. 
This data would be useful in final rule deliberations.
    While EPA recognizes that a discharge of less than 10,000 gallons 
can be harmful, regardless of how the NCP defines ``major discharge,'' 
EPA believes that it is reasonable to allow facilities with a capacity 
of no more than 10,000 gallons to prepare and implement a Plan that 
complies with the SPCC rule requirements and provides adequate 
protection against discharges without the involvement of a PE. These 
facilities generally have less complex operations and petroleum system 
configurations, and smaller oil storage capacities than other types of 
facilities subject to the SPCC requirements. Thus, the Agency believes 
that a responsible owner or operator at these facilities should be able 
to comply with the SPCC rule provisions without review and 
certification of the SPCC Plan by a PE, and that simplifying the rule 
will result in greater environmental protection by improving 
compliance.
b. Reportable Discharge History
    EPA proposes that a qualified facility subject to the SPCC 
requirements must have no reportable oil discharges as described in 
Sec.  112.1(b) during the ten years prior to self-certification or 
since becoming subject to the SPCC requirements, whichever is less. 
Facilities that have been subject to SPCC for less than ten years, 
including new facilities, would need to demonstrate no discharges as 
described in Sec.  112.1(b) only for the period they have been subject 
to SPCC. This criterion is based on a proposal regarding oil-filled 
electrical equipment submitted by the Utility Solid Waste Activities 
Group (USWAG), as described in the documents supplementing the 
September 20, 2004 NODA at 69 FR 56184. In its proposal, USWAG 
recognized that facilities that pose a risk, in terms of oil discharges 
in quantities that are harmful (reportable under 40 CFR part 110), 
should not be granted relief. USWAG specifically proposed a ten-year 
spill history as a potential criterion to be eligible for relief. In 
general, NODA commenters expressed strong support for the USWAG 
proposal. As in the case of oil-filled operational equipment, the 
Agency believes that a clean spill history is a suitable criterion for 
demonstrating eligibility for Plan self-certification, while still 
effectively maintaining good prevention practices.
    Part 110 defines a discharge of oil in such quantities that may be 
harmful to the public health, welfare, or the environment of the United 
States as a discharge of oil that violates applicable water quality 
standards; a discharge of oil that causes a film or sheen upon the 
surface of the water or on adjoining shorelines; or a discharge of oil 
that causes a sludge or emulsion to be deposited beneath the surface of 
the water or adjoining shorelines (40 CFR 110.3). The Agency refers to 
such discharges in Sec.  112.1(b) of the rule. Any person in charge of 
a facility must report any such discharge of oil from the facility to 
the National Response Center (NRC) at 1-800-424-8802 immediately. While 
EPA recognizes that past release history does not necessarily translate 
into a predictor of future performance, the Agency believes that 
discharge history is a reasonable indicator of a facility owner or 
operator's ability to develop an SPCC Plan for the facility without the 
involvement of a PE. Hence, EPA proposes to use a facility's discharge 
history as a qualification criterion indicating the facility's ability 
to effectively develop and implement its SPCC Plan. By establishing a 
good oil spill prevention history, a facility qualifies for the self-
certification option offered in this proposal.
    The Agency requests comments on the appropriateness of a reportable 
discharge history criterion for determining the qualification of a 
facility for the self-certification option, whether it is necessary, 
and whether there are other indicators of a facility's effective 
implementation of the oil pollution prevention requirements under part 
112 that should be considered. In addition, the Agency also 
specifically requests comments on the proposed ten-year period for 
which facilities would be required to have had no reportable discharges 
in order to meet this qualification. The Agency requests that any 
alternative criterion or time period suggested include an appropriate 
rationale and supporting data to assist the Agency in considering them 
for final action. The Agency is also aware that events such as natural 
disasters, acts of war or terrorism, sabotage, or other calamities, 
beyond the control or planning ability of the facility owner or 
operator, may cause a reportable oil discharge. The Agency therefore 
requests comments on how to account for such occurrences in the 
discharge history criterion.
2. Proposed Requirements for Qualified Facilities
a. Self-Certification and Plan Amendments
    Some in the regulated community, particularly facilities with 
relatively smaller volumes of oil, identified the cost of the PE 
certification of SPCC Plans as one of its major concerns. This view was 
echoed in the comments submitted in response to the NODAs. The Agency 
has reviewed the requirements in light of the information provided and 
today proposes to allow for self-certification of SPCC Plans by owners 
and operators of qualified facilities. With this proposal, the Agency 
is responding to those concerns. The elements of the proposed self-
certification requirement are very similar in scope to those of the PE 
certification: owners and operators that choose to self-certify their 
Plans must certify that they are familiar with the requirements of the 
SPCC rule; they have visited and examined the facility; the Plan has 
been prepared in accordance with accepted and sound industry practices 
and standards; procedures for required inspections and testing have 
been established; the Plan is being fully implemented; the facility 
meets the qualification criteria set forth under Sec.  112.3(g)(1); the 
Plan does not include any environmental equivalence measures as 
described in Sec.  112.7(a)(2); the Plan contains no determinations of 
impracticability under Sec.  112.7(d); and the Plan and the 
individual(s) responsible for implementing the Plan have the full 
approval of management and the facility has committed the necessary 
resources to fully implement the Plan. The self-certification provision 
would be optional. Under today's proposal, an owner or operator of a 
qualified facility could choose to comply with the current requirements 
under part 112 if that is more suitable to his/her particular 
situation.
    Qualified facilities that choose to self-certify would not 
automatically lose eligibility for a self-certified Plan and be 
required to obtain PE certification in the event of a discharge as 
described in Sec.  112.1(b). EPA has the authority to require SPCC Plan 
amendments under Sec.  112.4. Section 112.4(a) requires a facility that 
has discharged more than 1,000 gallons of oil in a single discharge as 
described in 40 CFR part 110, or that has discharged more than 42 
gallons of oil in each of two discharges as described in 40 CFR part 
110 in any 12-month period, to submit information to

[[Page 73530]]

the EPA Regional Administrator (RA) within 60 days of the date of the 
discharge. As per Sec.  112.4(d), the RA may require the facility to 
amend its SPCC Plan in order to prevent and contain discharges, and the 
RA could require a facility to obtain PE-certification of its SPCC 
Plan. In addition, a discharge of oil ``in such quantities as may be 
harmful'', as defined in 40 CFR 110.3 that does not trigger the 
reporting requirements of Sec.  112.4(a) must still be reported to the 
National Response Center. Criminal action can be taken against an owner 
or operator of a facility if discharges are not reported. EPA also 
receives copies of the NRC reports and has the authority under Sec.  
112.1(f) to require a facility to prepare and implement an SPCC Plan or 
any applicable part of a Plan. The time frame for this review and 
amendment process is described in Sec.  112.4. The facility may choose 
to appeal the RA's decision to require a Plan amendment under Sec.  
112.4. The RA also has authority to require preparation and 
implementation of a Plan or applicable part of a Plan under Sec.  
112.1(f).
    The Agency requests comment on the appropriateness of using the 
existing authorities under the SPCC regulations rather than 
establishing a separate process that would automatically require a 
facility to obtain PE review and certification of the facility's SPCC 
Plan in the event of a reportable discharge. The Agency requests that 
any alternative approaches presented include an appropriate rationale 
and supporting data in order for the Agency to be able to consider them 
for final action.
    Under Sec.  112.5 of the SPCC rule, an owner or operator must 
review and amend the SPCC Plan following any change in facility design, 
construction, operation or maintenance that materially affects its 
potential for a discharge as described in Sec.  112.1(b). A PE must 
then certify any and all of these technical amendments to the SPCC 
Plan, as currently required under Sec.  112.3(d). Under today's 
proposal, technical amendments to SPCC Plans of qualified facilities 
would not be required to be certified by a PE. Instead, an owner or 
operator would be allowed to self-certify technical amendments to the 
Plan under the proposed Sec.  112.3(g)(2) provision, and facilities 
with PE-certified Plans which qualify for self-certification would be 
allowed to choose to self-certify future technical amendments rather 
than hire a professional engineer to certify the technical amendment. 
Facilities would be required to document the self-certification of a 
technical amendment in the SPCC Plan in accordance with Sec.  
112.3(g)(2).
b. Environmental Equivalence and Impracticability Determinations
    Under Sec.  112.7, facility owners and operators have the 
flexibility to deviate from specific rule provisions if the Plan states 
the reason for nonconformance and if equivalent environmental 
protection is provided by some other means of spill prevention, control 
or countermeasure. These ``environmentally equivalent'' measures must 
be described in the SPCC Plan, including how the equivalent 
environmental protection will be achieved based on good engineering 
practice. Allowance for ``environmentally equivalent'' deviations is 
provided in Sec.  112.7(a)(2) and are only available for requirements 
not related to secondary containment, such as fencing and other 
security measures, preventing catastrophic tank failure due to brittle 
fracture, integrity testing, and liquid level alarms. As part of the 
SPCC Plan, any environmentally equivalent measures are also required to 
be certified by a PE. The PE's SPCC Plan certification requirements 
include consideration of industry standards for the Plan, which would 
include equivalent environmental protection measures.
    The SPCC rule also provides flexibility for owners/operators who 
determine that the general secondary containment requirements in Sec.  
112.7(c) or any of the applicable additional requirements for secondary 
containment in subparts B and C are impracticable. Where 
impracticability is demonstrated, the SPCC rule allows facility owners 
and operators the flexibility to instead develop a contingency plan and 
comply with additional requirements as described in Sec.  112.7(d). The 
SPCC Plan must explain why containment measures are not practicable, 
provide an oil spill contingency plan that follows the provisions of 40 
CFR part 109 (Criteria for State, Local and Regional Oil Removal 
Contingency Plans), and provide a written commitment of manpower, 
equipment, and materials required to expeditiously control and remove 
any quantity of oil discharged that may be harmful as described in 40 
CFR part 110. A PE must certify any impracticability determinations, as 
well as the contingency plan and additional measures implemented in 
lieu of containment. Because of the expertise that a PE has in 
evaluating whether particular measures provide equivalent environmental 
protection and in knowing how to effectively implement such measures, 
EPA believes that the flexibility in these performance-based provisions 
is best suited to SPCC Plans that are reviewed and certified by a PE.
    Today's proposed amendment would allow qualified facilities to opt 
out of the PE certification, but would not allow facilities that take 
advantage of this option to include environmentally equivalent measures 
in their SPCC Plans pursuant to Sec.  112.7(a)(2). EPA is proposing 
this limitation on qualified facilities because EPA believes that in 
general, without the advantage of the expertise and knowledge that a PE 
brings to the development of an SPCC Plan, deviations based on 
environmental equivalence may not be adequate. However, as discussed 
below, EPA believes that allowing certain deviations may be appropriate 
for at least some owners of qualified facilities, without employing PE 
expertise. Therefore, EPA is proposing to allow certain deviations with 
respect to facility security and integrity testing of bulk storage 
containers.
    EPA is also proposing that qualified facilities be precluded from 
claiming impracticability and using contingency planning in lieu of 
secondary containment. EPA believes that a PE's knowledge and expertise 
is needed for appropriate contingency planning and other measures that 
must be put in place in the absence of secondary containment. Thus, 
requiring qualified facilities that opt out of PE certification to 
adhere to the current set of requirements would maintain the same 
standard of environmental protection provided in the existing rule.
    Today's proposal would not preclude a qualified facility from 
choosing environmentally equivalent measures or from demonstrating 
impracticability with respect to secondary containment requirements, 
although the qualified facility would need to comply with the current 
SPCC requirements (including the PE certification) in order to utilize 
the flexibility offered by PE-developed impracticability determinations 
and environmentally equivalent measures. In some circumstances, it may 
be more cost effective for a PE to prepare an SPCC Plan which utilizes 
environmentally equivalent measures or contingency planning, than for 
the owner/operator to comply with the SPCC provisions as outlined in 
today's proposal. Also, facilities with unconventional operations which 
qualify for this alternative may find that the current rule requirement 
for PE certification offers a more cost-effective method of achieving 
compliance because it provides additional flexibility through 
performance-based provisions. The Agency requests comments on the

[[Page 73531]]

appropriateness of restricting the use of impracticability 
determinations and environmentally equivalent measures by those 
qualified facilities that choose the option of self-certification in 
order to ensure an adequate level of environmental protection. Any 
alternative approach presented must include an appropriate rationale 
and supporting data in order for the Agency to be able to consider it 
for final action.
c. SPCC Plan Exceptions
    Today's proposal for self-certification of qualified facilities 
would restrict the use of alternative environmentally equivalent 
measures for qualified facilities that elect to develop their SPCC Plan 
without the services of a PE. The Agency's concern is that these 
facilities would no longer have a trained professional, with knowledge 
to make site-specific equivalence determinations, reviewing and 
certifying their Plan. However, EPA recognizes that some of the 
prescriptive provisions in the current regulatory requirements may 
prove difficult for some qualified facilities to meet.
    While the Agency still believes that generally allowing use of 
environmentally equivalent measures in self-certified Plans is not 
appropriate, some degree of flexibility in two areas may be appropriate 
for qualified facilities. The Agency believes that it can allow 
qualified facilities to comply with a streamlined set of basic security 
measures and integrity testing requirements. The flexibility in these 
proposed exceptions would be analogous to the flexibility provided 
under Sec.  112.7(a)(2), which allows for deviations from Sec.  
112.7(g) (security) and Sec.  112.8(c)(6) (integrity testing) that 
would not be available for these facilities under today's proposal.
    EPA recognizes that there is no one single approach to ensure 
proper facility security. For example, the security requirements of 
fencing and lighting may not always be appropriate for sites such as a 
national, state or local park subject to SPCC, where the site layout 
may be too extensive to fence, and where perhaps the lighting of a 
solitary field tank would invite, rather than deter, would-be 
intruders. Qualified facilities, in lieu of the requirements under 
Sec.  112.7(g) of this part, would be allowed to prepare a security 
plan that describes how the facility controls access to the oil 
handling, processing and storage areas; secures master flow and drain 
valves; prevents unauthorized access to starter controls on oil pumps; 
secures out-of-service and loading/unloading connections of oil 
pipelines; prevents acts of vandalism; and assists in the discovery of 
oil discharges. (Note that the security requirements in Sec.  112.7(g) 
do not apply to production facilities.)
    Today's proposal would allow a qualified facility to develop a 
general security plan that provides equivalent environmental protection 
to the requirements in Sec.  112.7(g). The Agency recognizes that these 
security provisions can be approached differently by the variety of 
facilities that would qualify for self-certification under today's 
proposal. It should be noted that this is an option and a qualified 
facility in compliance with the current requirements under Sec.  
112.7(g) would not be required to develop a security plan under the 
proposed Sec.  112.3(g).
    The security plan would be required to address how the owner or 
operator will:
     Secure all bulk storage containers, piping and oil-filled 
equipment from unauthorized access or acts of vandalism which could 
result in a discharge of oil;
     Secure appurtenances (valves and/or drains) in the closed 
position to prevent the flow of the contents of the container which 
could result in a discharge of oil;
     Secure pump controls in the ``off'' position when not in 
use and locate facility pump controls to prevent unauthorized access;
     Secure all loading or unloading transfer connections for 
facility piping; and
     Address whether security lighting is appropriate to both 
ensuring the discovery of oil discharges, and deter vandalism.
    This security plan would be required to be documented in the 
qualified facility's SPCC Plan, and would include a discussion of how 
the security plan will be implemented and the required training/
inspections/maintenance for security related equipment and activities. 
The Agency recognizes the unique nature of many of the facilities that 
would qualify for Plan self-certification, and as such, some 
flexibility is appropriate so these facilities can achieve compliance 
with the security provisions of the current SPCC rule. The application 
of the SPCC security measures is often determined by the facility's 
geographical/spatial factors and there is no ``one-size-fits-all'' 
answer to this serious compliance requirement. For example, facilities 
such as farms or national parks may have unique characteristics that 
make compliance with the current security measures, such as potentially 
fencing the entire facility footprint, inappropriate.
    The Agency is also proposing to provide flexibility in the area of 
integrity testing for qualified facilities. The Agency continues to 
believe that owners and operators should rely on the appropriate use of 
industry standards for the integrity testing requirements. As EPA 
stated in its May 2004 letter to the Petroleum Marketers Association of 
America (available at http://www.epa.gov/oilspill/pdfs/PMAA_letter.pdf
), the Agency recognizes that in certain site-specific 

circumstances, visual inspection may be appropriate and sufficient for 
compliance with the integrity testing requirement. The Agency expects 
that the selection of particular testing methods to comply with the 
integrity testing requirements in the current rule and today's proposal 
would be based on industry inspection standards such as the Steel Tank 
Institute (STI) SP-001, American Petroleum Institute (API) Standard 653 
and API Recommended Practice 12-R1. These industry standards address 
the qualifications of the tank inspector and the scope/frequency of the 
testing/inspections. Thus, in effect, the Agency is proposing to allow 
owners and operators of qualified facilities to consult and rely on 
industry standards or qualified container inspectors/testing personnel 
to determine the appropriate qualifications for tank inspectors/testing 
personnel and the type/frequency of integrity testing required for a 
particular container size and configuration. The Agency is proposing to 
allow qualified facilities to make this determination in accordance 
with industry standards without the need to develop a PE-approved 
environmentally equivalent deviation, as is currently required under 
Sec.  112.7(a)(2). The Agency believes that allowing this flexibility 
for qualified facilities would increase compliance and thus 
environmental protection.
    The U.S. Small Business Administration (SBA) Office of Advocacy has 
suggested an additional alternative approach for allowing flexibility 
for integrity testing of small shop-built tanks that is based on the 
current SP001 standard. The current SP001 standard allows periodic 
visual inspections for shop-fabricated aboveground storage tanks with a 
total capacity of 5,000 gallons, and for which there is spill control 
and a continuous release detection method (i.e., Category 1 tanks). SBA 
Office of Advocacy has suggested that EPA allow periodic visual 
inspections for shop-fabricated aboveground storage tanks at qualified 
facilities, in accordance with this SP001 standard, but broaden the 
applicability

[[Page 73532]]

to include shop-fabricated aboveground storage tanks that have an oil 
capacity of between 5,000 and 10,000 gallons. In all other respects, 
the SP001 standard would apply. In the SBA's view, due to the presence 
of spill control and a continuous release detection method (in 
accordance with the SP001 standard), there appears to be little 
likelihood for a discharge into navigable waters. The SBA Office of 
Advocacy also believes this additional option would make the visual 
inspection option available to all, and not a subset of, qualified 
facilities and it would benefit those qualified facilities having one 
tank above 5,000 gallons.
    EPA is not proposing the SBA additional approach for several 
reasons. First the SBA approach would deviate from the industry 
standards noted above. Second, the Agency is unaware of a technical 
basis to justify this deviation. EPA must justify divergence from 
accepted industry standards under the National Technology Transfer and 
Advancement Act (NTTAA) (see section VII (I) for a description of 
NTTAA). Third, industry standards are periodically updated and revised 
to account for changes in technology and to remain consistent with good 
engineering practice while this approach would need to be revised 
through rulemaking. Finally, EPA believes that by allowing for a 
deviation from existing industry standards, compliance would become 
more complex as facilities try to understand the circumstances under 
which this additional approach can be employed. The Agency welcomes 
comment on this additional approach as well as on the proposed approach 
for integrity testing for qualified facilities. In addition, once the 
modifications proposed today are promulgated, the Agency is willing to 
continue to work with industry tank inspection standard setting 
organizations to update applicable industry standards. Commenters who 
have information on the scope and criteria associated with the industry 
visual inspection standards should provide it to the standards setting 
organizations and their national experts for consideration.
    At this time, EPA is aware that a number of industry standards are 
changing. Nevertheless, the Agency believes that it may be appropriate 
to allow the flexibility of alternative integrity testing methods for 
these qualified facilities to be consistent with relevant industry 
standards. For example, visual inspections may be appropriate for the 
lower volume shop-built containers in certain configurations that are 
likely to be present at most of these qualified facilities. In the 
absence of an environmental equivalency provision that would allow an 
alternative integrity testing method for qualified facilities, the 
owner or operator would be required to perform visual inspections plus 
non-destructive testing on all classes of containers, regardless of 
size and configuration. Qualified facilities would have to bear the 
cost and burden of conducting non-destructive testing that may not be 
necessary under industry standards. The Agency continues to strongly 
recommend that facilities, qualified for self-certification or 
otherwise, utilize industry standards that are appropriate to their 
particular tank configurations in developing and conducting tank 
inspection and testing programs and when determining inspector/testing 
personnel qualifications.
    The Agency requests comments on whether the proposed requirements 
for security and integrity testing for qualified facilities provide 
appropriate flexibility, while maintaining environmental protection. 
Any alternative approach presented must include an appropriate 
rationale and supporting data in order for the Agency to be able to 
consider it for final action.
3. Alternative Options Considered
    EPA considered other options for this proposal. These options 
included (1) providing an indefinite extension of deadlines or a 
suspension of all SPCC requirements; and (2) a multi-tiered structure 
of requirements based on a facility's total regulated storage based on 
the SBA proposal described in the Certain Facilities NODA published 
last year. The Agency also considered requiring qualified facilities to 
make a one-time notification to EPA they have been in operation or 
subject to the SPCC requirements for a period less than ten years from 
the time of Plan certification, and therefore could not show a ten-year 
clean spill history as a qualifier. All of these options would apply to 
a defined set of ``qualified facilities''.
a. Extension/Suspension Options
    Two additional options were considered: An indefinite compliance 
date extension and a suspension of all requirements. Both options would 
apply to a defined universe of ``qualified'' SPCC-regulated facilities. 
An indefinite extension would provide an undetermined future date for 
compliance with the rule. As in past extensions, all facilities that 
should have had a Plan as of August 16, 2002 would be required to be in 
compliance with the pre-2002 SPCC requirements during the interim 
period, including those that could potentially take advantage of 
today's qualified facilities proposal. A suspension of requirements for 
qualified facilities would provide relief for the affected universe 
until EPA takes further action.
    Both of these options would allow EPA more time to decide how to 
regulate qualified facilities without delaying compliance for the 
entire universe of SPCC-regulated facilities. In contrast, the proposed 
option would set forth explicit requirements for qualified facilities 
that reduce compliance costs within the current compliance date 
schedule. Because these options would only postpone the rule's 
requirements for qualified facilities and because the Agency believes 
that the modifications proposed today address the major concerns raised 
by facilities that store lower volumes of oil, EPA believes it 
appropriate to go forward with today's proposal.
b. Multi-Tiered Structure
    A multi-tiered structure option was developed in response to 
comments EPA received following publication of the NODA for facilities 
that handle oil below a certain threshold amount (69 FR 56182, 
September 20, 2004) and is based on a previous analysis prepared for 
the SBA Office of Advocacy (Jack Faucett Associates, 2004) (hereafter 
``SBA proposal''). This revised regulatory structure would not only 
relax requirements for PE certification, but also requirements for 
preparing an SPCC Plan itself, although under this approach, the 
facility would still be responsible for complying with the substantive 
requirements of the SPCC rule. It includes a tiered system based on the 
total storage capacity of a facility, as follows:
     Tier I would include facilities that handle between 1,321 
and 5,000 gallons of oil (total storage capacity). These facilities 
would not need a written SPCC Plan (and therefore no PE certification 
would be needed), but would have to adhere to all other SPCC 
requirements.
     Tier II would include facilities handling between 5,001 
and 10,000 gallons of oil (total storage capacity). These facilities 
would be required to have a written SPCC Plan, but the Plan would not 
need to be certified by a PE, and a PE site visit would not be 
required. Standardized plans could be adopted by a facility conforming 
to standard design and operating procedures, without requiring PE 
certification.
     Tier III would include the remaining SPCC-regulated 
facilities (total storage capacity greater than

[[Page 73533]]

10,000 gallons). These facilities would be required to have a written 
SPCC Plan certified by a PE, as currently required by the 2002 revised 
SPCC rule.
    SBA also suggested that EPA promulgate an interim final rule that 
excludes small facilities with storage of less than 10,000 gallons (the 
first two tiers of their three-tier approach) from SPCC Plan 
requirements, pending completion of the full notice and comment 
rulemaking for small facilities to develop the aforementioned tiered 
requirements. In order to provide environmental protection in the 
interim period, SBA recommended that EPA require: (1) Regular visual 
inspections of containers, (2) replacement or retirement of leaking 
tanks, and (3) compliance with the part 109 contingency plan 
requirements or their equivalent. In this manner (according to SBA), 
the EPA could address the reality of the extremely low SPCC compliance 
rate among small facilities, and would work toward creating a rule that 
small facilities would be likely to comply with. SBA stated that such a 
move would enhance, rather than detract from, environmental protection.
    This approach would provide different levels of regulatory relief 
based on total oil storage capacity alone, basing degree of risk on the 
surrogate measure facility size. Many commenters on the NODA supported 
this approach, which would reduce compliance costs by eliminating the 
PE certification requirement for facilities under 10,000 gallons. 
However, EPA believes that such an approach poses significant 
implementation problems both for the regulated community and the 
regulators. In particular, the Agency believes that without the owner/
operator developing a Plan or documentation on how the facility will 
comply or expects to comply with the SPCC requirements, it will be 
challenging for the facility to both meet the substantive requirements 
(for example, spill notification, response and preparedness planning, 
equipment maintenance, inspection and training, secondary containment), 
as well as provide documentation to the regulators that the facility is 
in compliance. Additionally, EPA inspectors conducting site visits 
would have no written Plan or documentation to assess the facility's 
effectiveness in implementing its spill prevention strategy.
    Although EPA received general comments supporting this option on a 
conceptual level, neither the information presented in the NODA nor the 
comments addressed the practical application of this alternative. The 
Agency welcomes comments on this approach, as well as on the proposed 
approach, the practical application of the proposal and the rationale 
for its adoption.
c. One-Time Notification
    The Agency recognizes that some facilities otherwise qualifying for 
owner/operator self-certification will have been in existence for fewer 
than ten years and will consequently be unable to demonstrate ten years 
without a discharge as described in Sec.  112.1(b). Some of these 
facilities will have come into existence after August 16, 2002, and 
will not have been subject to SPCC regulation until August 18, 2006; 
some will be new facilities beginning operation after that date. EPA 
agrees with the USWAG comments that a compliant discharge history of 
ten years or more provides a higher degree of assurance of continuing 
compliance than a history of ten years or less. This is particularly 
true when comparing ten-year compliant facilities to otherwise 
qualified facilities which began operations after August 16, 2002, and 
whose owners or operators, to date, have not been subject to the 
requirements of the SPCC program, as well as start-up facilities 
without any operating history. EPA considered whether owners or 
operators of newer facilities that do not have ten years of compliance 
and operation without a discharge should be required to provide a one-
time notification to the Agency. This notification would be submitted 
to the Administrator within 30 days of self-certifying a facility's 
SPCC Plan and would include the following information: (1) Name of the 
facility owner/operator; (2) mailing address of the facility owner/
operator; (3) type of business conducted at the facility that is 
subject to the requirements of this part; (4) above-ground capacity of 
the facility; (5) location of the facility by street address or, if 
there is no street address, by longitude and latitude; and (6) year the 
facility began operations. These notices could be provided by either 
regular or electronic mail. The Agency would have the opportunity to 
provide some basic SPCC outreach and educational support to these 
owners and operators who, while otherwise demonstrating the 
prerequisites for self-certification, are unable to demonstrate ten 
years without a discharge as described in Sec.  112.1(b). This one-time 
notification requirement, if adopted, would modify today's proposed 
qualified facilities option by increasing its burden for some 
facilities. EPA decided not to pursue this option because it does not 
differ substantively from the proposed action and the additional burden 
of a notification requirement was not considered necessary.
    The Agency welcomes comments on these or other alternatives that 
could serve to reduce the burden to smaller oil-handling facilities in 
particular, while at the same time maintaining appropriate levels of 
environmental protection by preventing discharges of oil. Any 
alternative approach presented must include an appropriate rationale 
and supporting data in order for the Agency to be able to consider it 
for final action.

B. Qualified Oil-Filled Operational Equipment

    EPA proposes to amend the Oil Pollution Prevention regulation (40 
CFR part 112) to provide a definition of oil-filled operational 
equipment and an optional alternative to the general secondary 
containment requirements for oil-filled operational equipment that 
meets the qualifying criterion (hereafter referred to as ``qualified 
oil-filled operational equipment''). The proposal would allow owners 
and operators of facilities with qualified oil-filled operational 
equipment to have the alternative of preparing an oil spill contingency 
plan and a written commitment of manpower, equipment and materials to 
expeditiously control and remove any oil discharged that may be 
harmful, without having to make an individual impracticability 
determination as required in Sec.  112.7(d). The owner or operator 
would also be required to establish and document an inspection or 
monitoring program for this qualified oil-filled operational equipment 
to detect equipment failure and/or a discharge, in lieu of providing 
secondary containment.
    EPA proposes to add Sec.  112.7(k) to define the SPCC eligibility 
criterion that qualified oil-filled operational equipment must meet in 
order to be considered qualified oil-filled operational equipment. 
Eligibility of a facility with oil-filled operational equipment would 
be determined by considering the reportable discharge history from any 
oil-filled operational equipment. The qualified oil-filled operational 
equipment criterion specifically requires that the facility had no 
discharges as described in Sec.  112.1(b) from any oil-filled 
operational equipment in the ten years prior to the SPCC Plan 
certification date, or since becoming subject to 40 CFR part 112 if the 
facility has been in operation for less than ten years.
    This proposed action would provide an alternative means of SPCC 
compliance for this equipment;

[[Page 73534]]

therefore, an owner/operator could choose to follow the current SPCC 
requirements to provide secondary containment for each piece of 
qualified oil-filled operational equipment in accordance with Sec.  
112.7(c) if desired. For example, oil-filled operational equipment at 
electrical substations is often surrounded by a gravel bed, which 
serves as a passive fire quench system and support for the facility 
grounding network and can provide a restriction to movement of any oil 
that may be released. Gravel beds, if designed to prevent a discharge 
as described in Sec.  112.1(b) (i.e., drainage systems that do not 
serve as a conduit to surface waters) may meet the general secondary 
containment requirements of Sec.  112.7(c). EPA further notes that 
facilities with oil-filled operational equipment located within 
buildings with limited drainage, which prevents a discharge as 
described in Sec.  112.1(b), may already meet the requirements for 
general secondary containment of Sec.  112.7(c). If so, a contingency 
plan for this equipment is not necessary. Ultimately, this would be a 
decision by the owner and/or operator.
1. Proposed Oil-Filled Operational Equipment Definition
    In July 2002, EPA clarified that oil-filled equipment (i.e., oil-
filled electrical, operating, and manufacturing equipment) are not bulk 
storage containers and therefore are not subject to the bulk storage 
container provisions in Sec.  112.8(c), including specifically sized 
secondary containment for bulk storage containers and integrity 
testing. However, as EPA stated in the preamble to the July 2002 
amendments, oil-filled equipment is subject to general secondary 
containment requirements described in Sec.  112.7(c), which can be 
provided by various means including drainage systems, spill diversion 
ponds, etc. EPA believes these measures provide for safety and also 
meet the needs of section 311(j)(1)(C) of the CWA.
    Though there are times when general secondary containment is 
practicable for oil-filled operational equipment, the Agency agreed to 
continue to evaluate whether the general secondary containment 
requirements found in Sec.  112.7(c) should be modified for small 
electrical and other types of equipment which use oil for operating 
purposes. On September 20, 2004, EPA published a NODA which made 
available and solicited comments on submissions to EPA suggesting that 
alternate regulatory requirements for facilities with oil-filled and 
process equipment would be appropriate (69 FR 56184). EPA has reviewed 
the public comments and data submitted in response to this NODA and 
presents today's proposal in accordance with our intention to consider 
alternative containment options for electrical and operational 
equipment.
    Today's proposal defines oil-filled operational equipment as 
``equipment which includes an oil storage container (or multiple 
containers) in which the oil is present solely to support the function 
of the apparatus or the device. Oil-filled operational equipment is not 
considered a bulk storage container, and does not include oil-filled 
manufacturing equipment (flow-through process).'' Examples of oil-
filled operational equipment include, but are not limited to, hydraulic 
systems, lubricating systems (e.g., those for pumps, compressors and 
other rotating equipment, including pumpjack lubrication systems), gear 
boxes, machining coolant systems, heat transfer systems, transformers, 
circuit breakers, electrical switches, and other systems containing oil 
to enable the operation of the devices.
    Oil-filled operational equipment differs from bulk storage 
containers in several ways. Oil-filled operational equipment typically 
has minimal oil throughput because such equipment does not require 
frequent transfers of oil. Further, the oil contained in oil-filled 
operational equipment, such as cooling or lubricating oil, is intrinsic 
to the operation of the device and facilitates the function of the 
equipment. A leak of oil from some oil-filled operational equipment can 
be detected by low-level alarms and remote monitoring of the 
performance of the equipment. For example, the loss of oil from 
electrical equipment will result in the equipment ceasing to operate, 
which will result in a power outage. Utilities have strong economic 
incentives to prevent power outages, to discover and respond to an 
outage, and to correct the conditions that produced the outage as 
quickly as possible. In addition, oil-filled operational equipment is 
often subject to routine maintenance and inspections to ensure proper 
operation. Finally, oil-filled operational equipment is designed, 
constructed, and maintained according to specifications for its 
particular operation and construction materials are corrosion-
resistant.
    However, the oil storage capacity of oil-filled operational 
equipment still counts towards the total oil storage capacity of the 
facility. The SPCC regulation defines storage capacity of a container 
as the shell capacity of the container. This definition applies to all 
oil storage containers including bulk storage containers and all oil-
filled equipment. In order to determine the storage capacity of an 
individual piece of oil-filled operational equipment, the owner/
operator would consider the total storage capacity of the piece of 
equipment (i.e., add together the capacity of multiple compartments or 
reservoirs of oil storage). The owner or operator must include the 
storage capacity of oil-filled operational equipment in order to 
determine applicability of the SPCC regulation to the facility.
    As proposed today, oil-filled manufacturing equipment (which 
involves a flow-through process) would not qualify for this 
alternative. Under the current rule, oil-filled manufacturing equipment 
(which is a subset of oil-filled equipment) is not defined as a bulk 
storage container. Oil-filled manufacturing equipment includes, for 
example, process vessels, conveyances such as piping associated with a 
process, and equipment used in the alteration, processing or refining 
of crude oil and other non-petroleum oils, including animal fats and 
vegetable oils Oil-filled manufacturing equipment is inherently more 
complicated than oil-filled operational equipment because it typically 
involves a flow-through process and is commonly interconnected through 
piping. For example, oil-filled manufacturing equipment receives a 
continuous source of oil, in contrast to the static capacity of other, 
non-flow-through oil-filled equipment.
    Today's proposal would not change any requirements for oil-filled 
manufacturing equipment. Oil-filled manufacturing equipment remains 
subject to the general SPCC requirements under Sec.  112.7, including a 
demonstration of impracticability under Sec.  112.7(d) if the SPCC Plan 
does not provide for secondary containment as required by Sec.  
112.7(c). The containers associated with storage of raw products, or 
the finished oil products are bulk storage containers and are not 
considered oil-filled manufacturing equipment or oil-filled operational 
equipment. Additionally, piping systems not associated with the 
alteration, processing or refining of crude oil and other non-petroleum 
oils, including animal fats and vegetable oils are not considered oil-
filled manufacturing equipment. EPA expects the owner/operator to 
delineate bulk storage containers from the oil-filled manufacturing 
equipment in the facility SPCC Plan (e.g., on the facility diagram and 
in discussion of compliance with inspection requirements of the rule). 
Additionally, while oil-filled manufacturing equipment is not a bulk

[[Page 73535]]

storage container and is therefore not subject to the frequent visual 
inspection requirement for bulk storage containers under Sec.  
112.8(c)(6), EPA believes that it is good engineering practice to have 
some form of visual inspection or monitoring for oil-filled 
manufacturing equipment in order to prevent discharges as described in 
Sec.  112.1(b). Furthermore, it is a challenge to comply with several 
of the SPCC provisions (for example, requirements for security under 
Sec.  112.7(g) and for countermeasures for discharge discovery under 
Sec.  112.7(a)(3)(iv)) without some form of inspection or monitoring 
program.
2. Eligibility Criteria--Reportable Discharge History
    Under today's proposal, the alternative to secondary containment 
for qualified oil-filled operational equipment would not be available 
to facilities that have had a reportable discharge from any oil-filled 
operational equipment in the ten years prior to the SPCC Plan 
certification date, or since becoming subject to 40 CFR part 112 if the 
facility has been in operation for less than ten years. This criterion 
is based on a proposal submitted by USWAG, as described in the 
documents supplementing the September 20, 2004 NODA at 69 FR 56184. In 
its proposal, USWAG recognized that facilities that pose a risk, in the 
form of discharges of oil in quantities that are harmful (reportable 
under 40 CFR part 110), should not be granted regulatory relief. In 
general, NODA commenters expressed strong support for the USWAG 
proposal.
    40 CFR 110.3 defines a discharge of oil ``in such quantities that 
may be harmful to the public health, welfare, or the environment of the 
United States as a discharge of oil that violates applicable water 
quality standards; a discharge of oil that causes a film or sheen upon 
the surface of the water or adjoining shorelines; or a discharge of oil 
that causes a sludge or emulsion to be deposited beneath the surface of 
the water or adjoining shorelines. The Agency refers to such discharges 
in Sec.  112.1(b) of the rule. Any person in charge of a facility must 
report any such discharge of oil from the facility to the National 
Response Center (NRC) at 1-800-424-8802 immediately. While EPA 
recognizes that past discharge history does not necessarily predict 
future performance, the Agency believes that discharge history can be 
used as a surrogate measure for a facility's ability to appropriately 
manage its oil. Hence, as with the ``qualified facilities'' proposal, 
EPA proposes to use this discharge history criterion to identify a 
facility's ability to effectively implement its SPCC Plan and prevent 
discharges in quantities that may be harmful. In establishing a good 
oil spill prevention history, a facility then qualifies for the oil 
spill contingency plan option offered in this proposal. Because the 
Agency is proposing to extend this relief to all oil-filled operational 
equipment, regardless of the oil storage capacity of the equipment, 
this criterion is critical in establishing an appropriate balance 
between environmental protection and burden relief by identifying those 
facilities which have demonstrated good spill prevention practices in 
the past.
    The Agency requests comments on the appropriateness of a reportable 
discharge history criterion for determining the qualifications of a 
facility with oil-filled operational equipment for this alternative, 
whether it is necessary, and whether there are other measures of a 
facility's effective implementation of the oil pollution prevention 
requirements for oil-filled operational equipment under 40 CFR part 112 
that should be considered. In addition, the Agency also specifically 
requests comments on the proposed ten-year period by which facilities 
can meet the discharge history criterion. Any alternative time periods 
suggested must include an appropriate rationale and supporting data in 
order for the Agency to be able to consider them for final action. The 
Agency is also aware that events such as natural disasters, acts of war 
or terrorism, sabotage, or other calamities, beyond the control or 
planning ability of the facility owner or operator, may cause a 
reportable oil discharge. The Agency therefore requests comments on how 
to account for such occurrences in the discharge history criterion.
3. Proposed Requirements for Qualified Oil-Filled Operational Equipment 
in Lieu of Secondary Containment
a. Contingency Plans and a Written Commitment of Manpower, Equipment 
and Materials
    The regulated community, particularly electrical facilities, 
identified secondary containment for oil-filled operational equipment 
as one of its major cost concerns. This sentiment was echoed in the 
comments submitted in response to the NODAs. With this proposal, the 
Agency is responding to those concerns by providing targeted relief 
without compromising on environmental protection. EPA believes that 
secondary containment may be often impracticable for oil-filled 
operational equipment due to inherent design and safety considerations, 
as well as site configuration. The oil associated with oil-filled 
operational equipment remains inside the equipment and transfers do not 
occur regularly; for oil-filled electrical equipment (e.g., 
transformers) transfers may occur infrequently, if at all. Operational 
equipment is designed, constructed, and maintained according to 
specifications for its particular operation and construction materials 
are corrosion-resistant. The complexity of the equipment and the nature 
of the use of this equipment may not lend itself to traditional bulk 
storage containment methods and thus flexibility is appropriate in this 
area and may improve compliance with oil pollution prevention measures. 
The proposed amendments to Sec.  112.7 would give a facility with 
qualified oil-filled operational equipment the option of implementing 
an oil spill contingency plan and written commitment of manpower, 
equipment, and materials required to expeditiously control and remove 
any quantity of oil discharged that may be harmful in lieu of secondary 
containment for this equipment, without having to make an 
impracticability determination for each piece of equipment. It should 
be noted that the use of a contingency plan does not relieve the owner/
operator of liability associated with an oil discharge to navigable 
waters or adjoining shorelines that violates the provisions of 40 CFR 
part 110.
    In the preamble to the 2002 amendments, EPA discusses how any 
facility which makes a determination of impracticability and has 
submitted a Facility Response Plan (FRP) under Sec.  112.20 is exempt 
from the contingency planning requirement because such a response plan 
is more comprehensive than a contingency plan following 40 CFR part 
109. The Agency believes that this should also apply to a facility with 
qualified oil-filled operational equipment which would choose to 
utilize contingency planning in lieu of secondary containment in 
accordance with today's proposal. If such a facility has already 
developed an FRP to comply with Sec.  112.20, then it would not need to 
also develop a contingency plan in accordance with 40 CFR part 109 for 
the qualified oil-filled operational equipment.
    Since, by definition, oil-filled operational equipment is not 
considered a bulk storage container, the facility owner or operator is 
not required to comply with the bulk storage requirements under Sec.  
112.8(c) or to conduct both periodic integrity testing of the 
containers and periodic integrity

[[Page 73536]]

and leak testing of the valves and piping as described under Sec.  
112.7(d). However, EPA believes that inspections or monitoring are 
important when there is no secondary containment in place. Therefore, 
EPA is proposing to require facilities with qualified oil-filled 
operational equipment choosing the proposed alternative to secondary 
containment to develop and implement an inspection or monitoring 
program, as further discussed in section B.3.b. of this section of the 
preamble. Since this proposal for qualified oil-filled operational 
equipment would provide an optional method of SPCC compliance, a 
facility with such equipment could choose to follow the current SPCC 
requirements and provide general secondary containment in accordance 
with Sec.  112.7(c) for this equipment if desired. Ultimately, this 
would be a decision of the owner and/or operator.
    Facilities with qualified oil-filled operational equipment that 
choose the proposed alternative to secondary containment and that 
subsequently experience a discharge would not automatically lose 
eligibility for today's proposed relief. Owners/operators of facilities 
which discharge oil in quantities that may be harmful from oil-filled 
operational equipment should re-evaluate the effectiveness of the SPCC 
Plan (specifically the contingency plan, written commitment of 
resources and inspections/monitoring alternative discussed in today's 
proposal) and determine the need for secondary containment measures in 
lieu of contingency planning. Additionally, the Regional Administrator 
(RA) may determine that a facility is no longer eligible to have a 
contingency plan in lieu of secondary containment without making an 
impracticability determination, and such facilities may be required to 
amend their Plans to provide secondary containment for their oil-filled 
operational equipment. The RA has the authority to require SPCC Plan 
amendments under Sec.  112.4. Section 112.4(a) requires a facility that 
has discharged more than 1,000 gallons of oil in a single discharge as 
described in 40 CFR part 110, or that discharged more than 42 gallons 
of oil in each of two discharges as described in 40 CFR part 110 in any 
12-month period to submit information to the RA within 60 days of the 
date of the discharge. As per Sec.  112.4(d), the RA has the authority 
to require the facility to amend its SPCC Plan in order to prevent and 
contain discharges; e.g., the RA may require a facility to install 
secondary containment for oil-filled operational equipment. In 
addition, a discharge of oil under 40 CFR part 110 that does not 
trigger the reporting requirements of Sec.  112.4(a) must still be 
reported to the National Response Center. EPA also receives copies of 
the NRC reports and has the authority under Sec.  112.1(f) to require a 
facility to prepare and implement an SPCC Plan or any applicable part 
of a Plan. Thus, the RA may require a Plan, partial Plan, or amendments 
to the Plan to achieve full compliance with the rule, as deemed 
appropriate to prevent further discharges in quantities that may be 
harmful.
b. Inspections or Monitoring Program
    Facility owners or operators that wish to take advantage of this 
proposed alternative would be required to develop an appropriate set of 
procedures for inspections or a monitoring program for qualified oil-
filled operational equipment. For facilities that rely on contingency 
planning in lieu of secondary containment for qualified oil-filled 
operational equipment, discharge discovery by inspection or monitoring 
is of paramount importance for effective and timely implementation of 
the contingency plan. An inspection or a monitoring program would 
ensure that facilities are alerted quickly of equipment failures and/or 
discharges. A written description of the inspection or monitoring 
program would be required to be included in the SPCC Plan. Under the 
existing requirement in Sec.  112.7(e), the owner or operator would be 
required to keep a record of inspections and tests, signed by the 
appropriate supervisor or inspector, for a period of three years. 
Records of inspections and tests kept under usual and customary 
business practices suffice (e.g., records of inspections and tests 
required by this rule may be maintained in electronic or any other 
format which is readily accessible to the facility and to EPA 
personnel).
    While oil-filled operational equipment is not a bulk storage 
container and is therefore not subject to the frequent visual 
inspection requirement for bulk storage containers under Sec.  
112.8(c)(6), EPA believes that it is good engineering practice to have 
some form of visual inspection or monitoring for oil-filled operational 
equipment in order to prevent discharges as described in Sec.  
112.1(b). Additionally, it is a challenge to comply with several of the 
SPCC provisions (for example, requirements for security under Sec.  
112.7(g) and for countermeasures for discharge discovery under Sec.  
112.7(a)(3)(iv)) without some form of inspection or monitoring program.
    A facility owner/operator must be able to quickly detect a 
discharge from qualified oil-filled operational equipment in order for 
a contingency plan to be effective. Oil-filled operational equipment 
may be frequently monitored by employees tending to the operation, and 
in such a case, discharges of oil would be noticed quickly. For many 
types of operational equipment, particularly oil-filled electrical 
equipment, releases of oil rapidly decrease the functionality of the 
equipment--for oil-filled electrical equipment, loss of dielectric 
fluid leads to equipment failure and an interruption of electric power 
transmission. The need for equipment reliability assures prompt 
detection of releases of oil, enhancing the probability of a prompt 
response action. Therefore, in lieu of secondary containment, today's 
proposal for qualified oil-filled operational equipment includes the 
requirement for a facility owner/operator to establish and document an 
inspection or monitoring program, in addition to the preparation of a 
contingency plan, and a written commitment of manpower, equipment, and 
materials to expeditiously control and remove oil discharged.
    The Agency requests comments on the appropriateness of this 
requirement as a qualification for this alternative, and whether there 
are other measures that a facility could take to ensure that a 
contingency plan is activated in a timely manner upon equipment failure 
or discharge. The Agency also requests comments on whether there are 
other requirements that should be added for facilities with oil-filled 
operational equipment to be able to establish and document an 
inspection or monitoring program, use a contingency plan, and provide a 
written commitment of manpower, equipment and materials in lieu of 
secondary containment for qualified oil-filled operational equipment. 
Any alternative approach presented must include an appropriate 
rationale and supporting data in order for the Agency to be able to 
consider it for final action.

Alternative Options Considered

    EPA considered alternative approaches to address streamlined 
requirements for small oil-filled operational equipment. One option was 
similar to the qualified facilities proposal, in which eligibility of a 
facility with oil-filled operational equipment would be determined by 
considering capacity thresholds and reportable discharge history from 
any

[[Page 73537]]

oil-filled operational equipment. Another option would call for a 
tiered set of requirements for electrical and other oil-filled 
operational equipment. EPA also considered options similar to those 
presented for the qualified facilities proposal: (1) providing an 
indefinite extension of the Plan revision and implementation dates for 
certain types of oil-filled operational equipment; and (2) suspending 
all SPCC requirements for certain types of oil-filled operational 
equipment.
a. Capacity Threshold Qualifier
    The Agency considered an alternative approach based on various 
levels of aggregate oil storage capacity at a facility for determining 
which facilities would be eligible for reduced burden as qualified oil-
filled operational equipment. EPA considered limiting the proposed 
option by including two alternative storage capacity thresholds from 
which the owner/operator may determine the equipment or facility's 
eligibility: (1) The storage capacity of an individual piece of oil-
filled operational equipment is 1,320 gallons or less, regardless of 
the facility's total oil-filled operational equipment aggregate 
capacity; or (2) the aggregate oil-filled operational equipment storage 
capacity at the facility is 10,000 gallons or less. EPA also considered 
an alternative range of thresholds for both an individual piece of oil-
filled operational equipment (ranging from 2,640 to 5,000 gallons) and 
for the facility aggregate capacity of 20,000 gallons in order to 
provide a greater degree of burden reduction than the alternative 
thresholds considered by EPA. In determining potential threshold 
capacities, EPA considered current thresholds in the rule, as well as 
proposals by industry. This was intended to limit this relief to small 
pieces of oil-filled operational equipment or to facilities storing 
smaller aggregate volumes of oil in oil-filled operational equipment. 
The total facility oil-filled operational equipment storage capacity 
threshold addresses the co-location of oil-filled operational equipment 
within a facility.
    The Agency decided not to propose a threshold criterion because we 
believe this equipment is unique and different from bulk storage 
containers and manufacturing equipment (flow-through process) such that 
the spill history alone suffices as a qualifying criterion to determine 
eligibility. The Agency was also concerned with the limited amount of 
information provided in response to the NODA. The data submitted in 
response to the NODA was primarily from the electrical industry and the 
Agency has no information describing the types of oil-filled 
operational equipment, capacities and distribution for other 
industries. Additionally, we have limited specific information on the 
various sizes of oil-filled electrical equipment to assist in 
establishing a threshold for an individual piece of equipment.
    The Agency seeks comments on whether eligibility for qualified oil-
filled operational equipment status should be based on a specific level 
of aggregate oil-filled operational equipment storage capacity at a 
given facility. The Agency seeks comments on whether a threshold 
criterion achieves an appropriate balance of facility burden and 
environmental protection for oil-filled operational equipment. Any 
available data specific to either the capacity, location, or size 
distribution of oil-filled operational equipment within a facility or 
within a specific industry sector would be useful in Agency 
deliberations for final rulemaking. Comments specific to establishing a 
threshold criterion for oil-filled operational equipment should include 
supporting data that: (1) Demonstrates why the suggested volume 
threshold is preferred; and (2) estimates the number (or percentage) of 
facilities that would be eligible for qualified oil-filled operational 
equipment status. Any alternative approach presented should include an 
appropriate rationale and supporting data in order for the Agency to be 
able to consider it for final action.
b. Multi-Tiered Structure
    The tiered structure option was considered in response to comments 
EPA received following publication of a Notice of Data Availability for 
oil-filled equipment (69 FR 56184, September 20, 2004) and is based on 
a previous proposal put forth by USWAG that focused on electrical 
equipment. A central element of this option would allow the facility 
owner or operator to define each discrete unit of this type of oil-
filled equipment as a facility. This option would also establish three 
tiers for regulated onshore oil-filled operational equipment based on 
the storage capacity of the equipment. Individual pieces of oil-filled 
operational equipment with an oil storage capacity of 1,320 gallons or 
less (Tier 1) would have been exempt from all SPCC requirements. For 
individual pieces of oil-filled operational equipment with a capacity 
greater than 1,320 but less than 20,000 gallons and which meet 
additional qualifying criteria (Tier II), facility owners and operators 
would have the option of preparing a contingency plan in lieu of an 
SPCC Plan. Such an approach would have exempted a significant portion 
of the regulated universe with oil-filled operational equipment from 
the development of an SPCC Plan entirely and instead would only need to 
develop a contingency plan and a written commitment of manpower, 
equipment and materials in the event of a discharge. Tier III would 
require that all other oil-filled operational equipment with capacities 
greater than 20,000 gallons for an individual piece of equipment be 
required to comply with the current SPCC rule.
    Although the Agency agrees that some regulatory modifications are 
appropriate for facilities containing oil-filled operational equipment, 
there is still a reasonable potential for discharge from this equipment 
and coverage by some type of SPCC Plan is warranted. The Agency 
believes this is true even for facilities composed entirely of oil-
filled operational equipment. EPA also has concerns about the 
suggestion to allow facility owners and operators to define each piece 
of oil-filled equipment as a separate facility because of the potential 
for greater rule complexity, implementation questions and confusion 
across the wide variety of facilities covered by the SPCC rule. For 
example, the Agency may have to define and develop criteria that would 
be used by the facility owner or operator to determine which equipment 
is a separate facility, which is not, and how the elements of a 
facility plan would address these differences. Uncertainty and 
confusion about the definition of a facility could lead to a greater 
lack of compliance and the potential for greater environmental harm.
c. Extension/Suspension Options
    EPA could propose an indefinite extension to the compliance dates, 
similar to the previous extensions already granted, that would apply to 
oil-filled operational equipment. This action would allow EPA more time 
to decide how to regulate oil-filled operational equipment without 
delaying compliance for the entire universe of SPCC-regulated 
facilities and equipment. However, the extension would be for a yet-to-
be-determined length of time, and for an unspecified set of 
requirements. Since so many facilities have oil-filled operational 
equipment, if changes to these requirements are delayed, a significant 
number of facilities might have to modify their existing Plans more 
than once to accommodate future rule changes. As with past extensions, 
EPA would continue to require that oil-filled operational equipment 
comply with pre-

[[Page 73538]]

2002 SPCC requirements during the interim period at facilities that 
should have had an SPCC Plan as of August 16, 2002, providing no 
immediate relief.
    A suspension of all requirements for oil-filled operational 
equipment would provide immediate relief until further notice and 
provided EPA with more time to decide how to regulate this equipment. 
The Agency is concerned that this option provides no environmental 
protection during the time that new requirements are developed.
    EPA welcomes comments on these or other alternatives that could 
reduce the burden at facilities with oil-filled operational equipment, 
while maintaining appropriate levels of environmental protection. The 
Agency is also interested in comments related to the application of the 
USWAG proposal to other types of oil-filled operational equipment. Any 
alternative approaches presented must include an appropriate rationale 
and supporting data in order for the Agency to be able to consider them 
for final action.

Qualified Facilities and Qualified Oil-Filled Operational Equipment 
Overlap

    Some facilities would meet the criteria for both qualified 
facilities and qualified oil-filled operational equipment. Such 
facilities would be able to benefit from both of the burden-reduction 
options proposed under today's action. The owner or operator could 
choose to develop a contingency plan and a written commitment of 
manpower, equipment and materials in lieu of secondary containment for 
qualified oil-filled operational equipment. Since no impracticability 
determination would be required for qualified oil-filled operational 
equipment, the owner or operator could self-certify his/her SPCC Plan 
and would not be required to have a PE develop and certify the 
contingency plan for the qualified oil-filled operational equipment. 
The responsibility of preparing a contingency plan and identifying the 
necessary equipment, materials and manpower to implement the 
contingency plan would fall on the owner or operator of the qualified 
facility.

C. Motive Power

    There are some motive power containers already exempt from the SPCC 
requirements based on the rule exemption for containers with an oil 
storage capacity of less than 55 gallons. However, there are certain 
motor vehicles (including aircraft) that contain oil in capacities 
greater than or equal to 55 gallons solely for the purpose of providing 
fuel for propulsion, or solely to facilitate the operation of the 
vehicle. The concept of ``motive power'' is not addressed in the SPCC 
regulations, but the EPA-DOT MOU in Appendix A to 40 CFR part 112 
specifically refers to the transportation of oil, not to transportation 
in the general sense. As a result, oil storage containers with a 
capacity greater than 55 gallons used for motive power fall under the 
SPCC rule and secondary containment and other SPCC requirements apply. 
However, EPA never intended to regulate motive power containers on 
buses, sport utility vehicles, small construction vehicles, aircraft 
and farm equipment, or facilities or locations such as heavy equipment 
dealers, commercial truck dealers, or certain parking lots that may be 
subject to the SPCC requirements (including bulk storage containment, 
inspection, and overfill protection) solely because of the presence of 
motive power containers. Nor does EPA intend to require facilities 
otherwise subject to the SPCC rule to include motive power containers 
in their Plans.
1. Definition of Motive Power
    EPA proposes to amend the Oil Pollution Prevention regulation (40 
CFR part 112) to exempt motive power containers, defined as ``onboard 
bulk storage containers used solely to power the movement of a motor 
vehicle, or ancillary onboard oil-filled operational equipment used 
solely to facilitate its operation.'' This definition is intended to 
describe containers such as the fuel tanks that are used solely to 
provide fuel for a motor vehicle's movement or the hydraulic and 
lubrication operational oil-filled containers used solely for other 
ancillary functions of a motor vehicle. This definition would not 
include transfers of fuel or other oil into motive power containers at 
an otherwise regulated facility, or a bulk storage container mounted on 
a vehicle for any purpose other than powering the vehicle itself, for 
example, a tanker truck or refueler. The definition of motive power 
containers would not include oil drilling or workover equipment. 
Specifically, it would not apply to the drilling or workover rigs 
themselves; however, other earthmoving equipment (such as a bulldozer, 
trucks, or earth-moving equipment) located at a drilling or workover 
facility would be included in the scope of the definition. Similarly, 
seismic exploration vehicles located at, for example, oil and gas 
drilling, workover and production facilities, would be included in the 
scope of the definition of motive power.
    The Agency is seeking comments on the proposed definition of motive 
power containers or if there are any other definitions for ``motive 
power'' that would be more suitable. Any alternative approach presented 
must include an appropriate rationale and supporting data in order for 
the Agency to be able to consider it for final action.
2. Proposed Exemption
    This proposed rule amendment would exempt motive power containers, 
as defined above, from SPCC rule applicability through a proposed 
additional paragraph under the general applicability section, Sec.  
112.1(d). Furthermore, these storage containers would not be counted 
toward facility capacity under Sec.  112.1(d)(2). EPA recognizes that 
there is a potential for an oil discharge as described in Sec.  
112.1(b) from motive power containers, such as from a breach in the 
fuel storage container, from an overfill event, or from a rupture of 
oil-filled operational equipment such as a hydraulic line on heavy 
construction equipment. EPA has the authority, under 311(j)(1)(C) of 
the CWA, to impose requirements to prevent oil discharges from motive 
power containers. The Regional Administrator has the option under Sec.  
112.1(f) to require facilities with motive power containers to prepare 
and implement an SPCC Plan or any applicable part, if a determination 
is made that it is necessary in order to prevent a discharge of oil 
into waters of the United States.
    EPA notes that although this proposal provides the fuel tanks and 
ancillary oil-filled operational equipment on motor vehicles with an 
exemption from SPCC requirements, oil transfer activities occurring 
within an SPCC covered facility would continue to be regulated. An 
example of such an activity would be the transfer from an onsite tank 
via a dispenser to motive power containers. This transfer activity is 
subject to the general secondary containment requirements of Sec.  
112.7(c), but is not subject to the requirements of Sec.  112.7(h), 
because it does not occur across a loading/unloading rack. Regulating a 
transfer between unregulated motive power containers and a regulated 
tank is required by Sec.  112.1(b), which requires that the SPCC rule 
apply to owners or operators of facilities that transfer oil and oil 
products. Another example would be an airport mobile refueler at an 
SPCC-regulated airport that transfers oil to motive power containers or 
to an aircraft. That transfer activity would again be subject to the 
general secondary containment requirements of Sec.  112.7(c), but not 
subject to the

[[Page 73539]]

requirements of Sec.  112.7(h), again because it does not generally 
occur across a loading/unloading rack.
    An onboard bulk storage container that supplies oil for the 
movement of a vehicle or operation of onboard equipment, and at the 
same time is used for the distribution or storage of this oil is not 
subject to this proposed exemption. For example, a mobile refueler that 
has an onboard bulk storage container used to distribute fuel to other 
vehicles on a site may also draw its engine fuel (for propulsion) from 
that container. Because EPA continues to consider bulk storage 
containers mounted on vehicles or towed by a vehicle (such as a typical 
cargo tanker truck) subject to certain transfer-related SPCC 
requirements, these containers are not subject to today's proposed 
exemption. As noted above, the exemption applies only to onboard bulk 
storage containers used solely to provide motive power or to facilitate 
the operation of the vehicle.
    EPA is not extending the exemption for motive power containers to 
oil drilling and workover equipment, including rigs. The Agency 
believes that due to the unique nature of oil drilling and workover rig 
operations and the large amounts and high flow rates of oil associated 
with these activities, it would not be appropriate or environmentally 
sound to exempt them from the SPCC requirements, and thus they should 
remain subject to 40 CFR part 112. The purpose of offering the 
exemption is to offer relief for a particular set of equipment (e.g., 
automobiles) that may be present at an otherwise regulated SPCC 
facility, and not to offer relief for facilities that may be mobile and 
move from place to place as in the case of a drilling or workover rig. 
Although drilling and workover equipment, including rigs, are not 
exempt, other motive power equipment located at drilling or workover 
facilities (e.g., trucks, automobiles, bulldozers, seismic exploration 
vehicles or other earth-moving equipment) would be exempted. The agency 
believes that the general protection and the spill response and 
planning activities provided at an otherwise regulated SPCC facility 
will help the facility to address the spills associated with these 
motive power containers. However, the specific provisions (such as 
blowout prevention) which are present in the current rule for drilling 
or workover rigs, need to be preserved to maintain an adequate level of 
environmental protection for these unique activities. Therefore, an 
exemption for drilling and workover equipment, including rigs, is 
inappropriate.
3. Alternative Options Considered
    EPA considered other options to address motive power containers 
greater than 55 gallons in size. These options included: (1) Exemption 
of all motive power containers, except motive power containers on 
aircraft and mining equipment, which would be subject to the general 
requirements under Sec.  112.7; (2) exemption of all motive power 
containers below a certain gallon threshold, with containers above this 
threshold remaining subject to the general requirements under Sec.  
112.7; and (3) exclusion of motive power containers only from the 
facility storage capacity calculation and bulk storage container 
requirements.
a. Equipment-Based Motive Power Exemption
    EPA could choose to exempt motive power containers, except 
containers on aircraft and mining equipment, from the requirements of 
40 CFR part 112. The majority of motive power containers would be 
exempt from the SPCC rule. EPA would require that the containers on 
aircraft and mining equipment be covered by the SPCC requirements 
because these containers typically have much larger volume than other 
motive power containers and potentially pose a greater threat to the 
environment in the event of a discharge as described in 112.1(b). 
However, in the context of motive power containers, there is no 
information on the degree of likelihood of a discharge from motive 
power containers of different oil storage capacities nor is there data 
available to EPA specific to mining and aircraft equipment discharges 
that would justify this option. Therefore, the Agency chose not to 
propose this option.
b. Threshold-Based Motive Power Exemption
    Another option considered was to exempt motive power containers 
with a capacity below a certain threshold, and requiring containers 
with a capacity above the established threshold to have appropriate 
containment under Sec.  112.7(c). Those motive power containers 
included in the rule would only be required to have general 
containment, and would be exempt from all other requirements in 
Sec. Sec.  112.7 and 112.8(c). However, EPA rejected this option 
because it has no basis for choosing an appropriate threshold for these 
containers and there is no data that clearly supports any specific 
quantity. In addition, it would still present implementation problems 
for those motive power containers that were subject to the regulation.
c. Exclusion From Storage Capacity Calculation
    EPA could exclude motive power containers from the storage capacity 
determination at a regulated facility and from the definition of bulk 
storage container to clarify that these containers are not counted 
towards the 1,320 gallon aboveground oil storage threshold for the 
regulation. Nevertheless, the facility would have to consider these 
containers in their overall facility SPCC Plan. Although motive power 
containers would not be considered bulk storage containers, they would 
be subject to the general requirements of the rule under Sec.  112.7, 
including the provision for secondary containment. The facility SPCC 
Plan would have to identify the presence of motive power containers on-
site, in addition to their reasonable potential for discharge as per 
Sec.  112.7(b). This option is more complex for the regulated community 
and is not a clear exemption of motive power containers.
    Each of these alternative options was rejected because they did not 
address the implementation issues with regulating motive power 
containers under the SPCC requirements. The Agency welcomes comments on 
these or other alternatives that could serve to reduce the burden for 
facilities with motive power containers, while at the same time 
maintaining appropriate levels of environmental protection. Any 
alternative approaches presented must include an appropriate rationale 
and supporting data in order for the Agency to be able to consider them 
for final action.

D. Airport Mobile Refuelers

    Airport mobile refuelers are vehicles that are used on an airport 
to refuel aircraft and ground service equipment. Their onboard bulk 
storage containers are used to transport and transfer fuel and are 
subject to the SPCC rule because they are containers used to store oil 
prior to use, while being used, or prior to further distribution in 
commerce. As such, they are subject to all applicable SPCC rule 
provisions, including the secondary containment provisions of Sec.  
112.8(c)(2) (applicable to all bulk storage containers) and Sec.  
112.8(c)(11) (applicable more specifically to mobile/portable bulk 
storage containers). These provisions require a secondary means of 
containment, such as a dike or catchment basin, sufficient to contain 
the capacity of the largest single compartment or container with 
sufficient freeboard to contain precipitation.

[[Page 73540]]

    Regulated community members in the aviation sector have expressed 
concern that requiring sized secondary containment for airport mobile 
refuelers is not practicable for safety and security reasons. They 
argue that requiring refuelers to park in specially designed secondary 
containment areas located within an airport's aircraft operations area 
could create a safety and security hazard because it entails grouping 
the vehicles or placing impediments in the operations area. In 
addition, they claim that requiring mobile refuelers to return to 
containment areas located within the airport's tank farm between 
refueling operations may increase the risk of accidents (and therefore 
accidental oil discharge), as the vehicles would travel with increased 
frequency through the busy aircraft operations area. They also claim 
that providing secondary containment for mobile refuelers during 
airport operations presents inherent difficulties and point to controls 
on design, inspection, maintenance and operation of mobile refuelers 
imposed by the Federal Aviation Administration's Advisory Circulars. 
For example, the storage containers on the mobile refuelers must be 
manufactured to U.S. DOT-406 specifications for pressure vessels (49 
CFR 178.346).
    EPA is aware that certain airports subject to FAA's regulations at 
14 CFR part 139 require certification by the FAA Administrator or his 
delegated agent. As part of this certification, the Agency understands 
that compliance with Uniform Fire Code requirements, among other 
requirements in 14 CFR part 139, must be detailed in the Airport 
Certification Manual to obtain FAA approval and thus an Airport 
Operating Certificate per part 139. The Agency understands that the 
applicable Uniform Fire Code includes National Fire Protection 
Association's (NFPA) 30, Flammable and Combustible Liquids Code, NFPA 
407, Standard for Aircraft Fuel Servicing and NFPA 415, Standard on 
Airport Terminal Buildings, Fueling Ramp Drainage, and Loading 
Walkways. In particular, NFPA 407 requires that aircraft fuel servicing 
vehicles and carts shall be positioned so that a clear path of egress 
from the aircraft for fuel servicing vehicles shall be maintained 
[5.12.1]. Further, in NFPA 415, the code specifically states that in no 
case shall the design of a drainage system of any aircraft fueling ramp 
allow fuel to collect on the aircraft fueling ramp or adjacent ground 
surfaces where it constitutes a fire hazard [5.1.4]. As such, EPA 
believes that subjecting mobile airport refuelers to the specifically 
sized secondary containment requirements at Sec.  112.8(c)(2) and (11) 
would directly conflict with the Uniform Fire Code applicable to fuel 
handling at airports. EPA believes, however, that these bulk storage 
containers should remain subject to the general secondary containment 
requirements at Sec.  112.7(c) as this provision affords sufficient 
flexibility to the owner/operator and certifying PE to select a spill 
prevention method that would not conflict with the applicable Uniform 
Fire Code. Thus, EPA is proposing to exempt airport mobile refuelers 
from the specifically sized secondary containment requirements for bulk 
storage containers in Sec.  112.8(c)(2) and (11). EPA believes that 
this exemption is appropriate for airport mobile refuelers, so as not 
to conflict with the specific Uniform Fire Code requirements for 
airport fueling activities, while preserving environmental protection 
(especially for fuel transfers associated with airport mobile 
refuelers), afforded by the spill prevention provisions outlined in 
Sec.  112.7(c). EPA also believes that this clarification for airport 
mobile refuelers applies to mobile refuelers operating at all airports, 
both those certified under 14 CFR part 139 and non-certified airports.
1. Definition of Airport Mobile Refueler
    EPA proposes to amend the Oil Pollution Prevention regulation (40 
CFR part 112) to exempt airport mobile refuelers from the requirements 
of Sec.  112.8(c)(2) and (11). In today's proposal, EPA defines an 
airport mobile refueler as ``a vehicle with an onboard bulk storage 
container designed for, or used to, store and transport fuel for 
transfer into or from an aircraft or ground service equipment.'' This 
definition is adapted from definitions in the U.S. DOT Federal Aviation 
Administration's Advisory Circular 150/5230-4 on Aircraft Fuel Storage, 
Handling, and Dispensing on Airports, and NFPA 407 for Aircraft Fuel 
Servicing. The definition is intended to describe vehicles of various 
sizes equipped with a bulk storage container such as a cargo tank (tank 
trucks, tank full trailers, tank semitrailers, etc.) that are used to 
fuel or defuel aircraft at airports.
2. Proposed Amended Requirements
    This proposed amendment would revise Sec.  112.8(c)(2) and (11) to 
specifically exempt airport mobile refuelers, as defined above, from 
these provisions. Since airport mobile refuelers are mobile or portable 
bulk storage containers, the other provisions of Sec.  112.8(c) would 
still apply. Secondary containment systems sufficient to contain the 
capacity of the largest single compartment or container with sufficient 
freeboard to contain precipitation would no longer be required. 
Notwithstanding, there is a potential for oil discharges as described 
in Sec.  112.1(b) from airport mobile refuelers. Indeed, there are 
documented cases of reportable discharges while fuel is transferred 
from storage into the mobile refuelers and during aircraft refueling 
activities. Fuel leaks have occurred while the mobile refueler is 
parked or idle. Therefore, the general secondary containment